This Policy is Under Development. If questions please contact Area Manger.
The purpose of this trouble-shooting guide is to assist you in diagnosing a Low Skid Voltage fault.
This procedure applies to all units that are currently in service in the field, at a repair shop, and in storage yards.
Before any work is performed a JSA must be completed according to Flogistix procedure along with any customer requirements before any work is started.
Help guide to trouble shooting a Low Skid Voltage fault.
Step 1: Start by checking your battery voltage. Battery voltage needs to be around 12 V on both batteries. If batteries are below that charge them until they are back to normal operating voltage. While charging check the serpentine belt and alternator pulley condition. If the belt is frayed or cracked it could cause you to have a slipping belt, not allowing the alternator to charge sufficiently. Also ensure the tension of the belt is set correctly, too much slack in the belt will cause the same issue. Replace if needed.
Step 2: Next you will test the battery. Using a load tester, apply it to your battery and test the battery. If the battery fails the load test it needs to be replaced due to not having enough capacity to operate under a load. If the battery is faulty then it most likely overloaded the alternator causing it to not charge sufficiently. The alternator output should be above 13 V while running without any charging cables applied. Follow the procedure below.
1.2. 3 Gas Engine Alternator/Charging System
Step 3: If battery needs to be replaced due to a failed load test, replace battery. After replacing or charging battery back to sufficient charge start the engine and begin the alternator test by using your digital multi-meter. Set the meter to measure in DC Voltage. After setting your meter apply the positive lead to the output wire of the alternator, then apply your negative lead to the frame of the alternator. If the reading is below 13 V the alternator will need to be replaced.
Did this correct your issue? If not, continue to step four.
Step 4: Next, if you are still getting a low voltage alarm verify the output wire from the alternator is not cut or burned and not allowing voltage through it. Also verify the nut is tight holding the wire in its termination.
If issues continue after using this diagnostic sheet, contact your area lead for further instruction.
Management - Management is responsible for implementing, supporting, and enforcing the requirements of this procedure to their respective locations/area.
EHSS - Responsible to assist in the implementation of this procedure and to review for effectiveness.
Employees, Contractors, Vendors, ETC. - Are responsible to follow the following requirements outlined in this procedure and ask for assistance
Employees should be aware that units could contain flammable and toxic gasses. Potential for the possible hazards of gas ignition or fire, hot surfaces & fluids, rotating equipment. Risk of possible concentration of H2S. Hazardous gases could be in the units pressure vessels, cooler, or associated piping and risk of inhalation of hazardous gas fumes. Environmental spill of compressor oil and possible production fluids
All Personal Protective Equipment (PPE) for normal Field Mechanical duties apply for this procedure. Four Gas Monitor, which is outlined in the Flogistix EHSS Manual, PPE Section 8, Procedure 8.3 This procedure applies to all units in service in the field, at a service shop, or in any storage yard.
Insure Flogistix personnel have proper safety certification as required by the Flogistix Customer.
Insure Flogistix personnel adhere to all Customers safety practices.
Proper use of required tools
All spills shall be handled immediately according to MSDS recommendations and the employee's level of training
Flogistix Service Technicians performing this task will properly dispose of any waste liquids or solids. Disposal of any fluids or solid waste will be disposed of properly according to Flogistix policy. Disposal of any fluids will be done at an approved or designed waste location. Disposal of solid waste from a compressor shaft seal change such as, oily rags, ETC, will be disposed of according to the local regulations regarding the disposal of oil soaked rags.
All employees shall be initially trained on the following topics:
Employee Personal Protective Equipment (PPE)
Lock Out Tag Out (LOTO) procedure according to Flogistix policy
MSDS Online System
Emergency and First Aid procedures
Methods and Observations that may be used to detect the presence or release of a hazardous chemicals or gas in the work place
Tools & Equipment Required
All employees performing Preventative Maintenance shall be required to have the listed tools to perform job tasks:
All required PPE according to Flogistix Safety Policy
Lock Out Tag Out LOTO items to properly perform LOTO procedure according to Flogistix policy
Basic Hand Tools
Digital Multi-Meter
Approvals
Field Service approved by:
Date:
Engineering approved by:
Date:
EHSS approved by:
Date: