Plans may call out to land the neutral wire in the center lugs, ignore this, Springs fails inspection for landing neutral wire. They float the neutral wire just about every time.
Customer Premise AC Disconnect placard sticker on the Disco. That placard sticker has to be yellow. All other areas need to be red.
El Paso County
Can upsize wire, will not fail inspection for this.
Neutral can land on the bar within the AC disconnect as long as the green ground screw in the AC disconnect on the bar is screwed in. The county prefers it this way for Fused disconnects.
PPRBD
1st of July all stickers will be required to be placards and will be required to be installed with a rivet, screw, or bolt.
Confirmed in september that we don't need engraved map placards (typ sticker Q)