It is when DC electricity accidentally leaks to the ground. This usually happens due to:
Damaged wires (unshielded or cut).
Defective solar modules or power optimizers.
Internal inverter faults.
Every time the inverter turns on, it checks the resistance between the DC wires and the ground.
The Rule: If the resistance is too low (less than 600kΩ for single-phase or 1MΩ for three-phase), the inverter triggers an error.
Do it immediately. These faults often happen in the morning due to moisture and can "disappear" once the sun dries things out. You want to catch it while the error is active.
Go to the Layout tab.
Right-click the inverter and select Info.
Look for "Last Isolation Value" (measured in KΩ).
Before troubleshooting on-site, you may check the isolation value in the SolarEdge monitoring platform.
In the Monitoring Platform site,
select Layout
Right-click on the inverter and select Info.
In the General parameter list, check the Last Isolation Value.
Step 2
Select Diagnostics
Open the Commissioning Menu.
Select Maintenance > Diagnostics > Isolation Status.
The screen will show the resistance value and if the fault is on the DC+ or DC- side.
Step 3
Select Isolation Status
Step 4
The value of the isolation resistance (in KΩ) will be displayed, also, if an error was detected, whether the fault is at DC+ or DC-
Step 1
Locate the Faulty String
If multiple strings are connected to the inverter, find the faulty string by connecting one string at a time to the inverter and checking if the error is still displayed
Step 2
Verify
Check each of the string separately to determine if there is more than one faulty string
Step 1
Access the Isolation Status Screen
In SetApp, from the Commissioning menu select Maintenance -> Diagnostics -> Isolation Status
Step 2
Location of the Isolation Fault
The value of the isolation resistance (in kΩ) indicates whether the fault is at DC+ or DC-:
0% indicates the fault is at the DC+ side
100% indicates the fault is at the DC- side
To identify the location of the faulty Power Optimizer:
Multiply the number of Power Optimizers in the string by the percentage value. The result is the module near which the fault occurred.
For example: In a string with 15 modules and Power Optimizers and a percentage value of 68% :
15*68% = 10.2
This means that the fault is near module #10, counted from the DC+ side.
Replace the faulty component(s) as determined by the troubleshooting process.
In this procedure, you can check the resistance of system components, drilling-down from string level, through Power Optimizer/module pairs, and finally a single component – a Power Optimizer or a module. You can also check the wiring between the components.
Equipment Needed
Insulation tester
Connector branch cable
Step 1
Turn OFF the Inverter
Turn OFF the inverter ON/OFF switch, and wait until SetApp indicates that the DC voltage is safe (<50V), or wait five minutes before continuing to the next step.
Step 2
Disconnect DC
Disconnect all the DC cables connecting the strings to the inverter or the Safety Switch.
Step 3
Test the Resistance
Test the resistance of the extension DC cables between the strings and the inverter (home-run cables):
Disconnect the home-runs at both ends and measure each wire by connecting it to the positive probe, while the negative probe remains connected to the ground.
If the wiring resistance is less than 200MΩ, the wire is faulty; replace any faulty wires.
If the wiring resistance is 200MΩ or more, the fault is in the string that was connected to this extension cable;
check the string (without the extension cable) as described in the following step.
Step 4
Test the String Resistance
Verify safe string voltage and current: max. 50V and 500mA.
Connect the positive and negative connectors of the first or last Power Optimizer in the string to the branch cable
Connect the positive probe of the insulation tester to the branch cable.
Connect the negative probe of the insulation tester to a ground point.
Select 500V testing on the insulation tester.
Test the insulation.
Step 5
String Insulation Results
If the resistance is less than 600kΩ in a single phase inverter or less than 1MΩ in a three phase inverter, a leakage is occurring. Continue checking this string’s components to isolate the source of leakage, as detailed in the following steps.
Step 6
Test the Power Optimizers and Modules
Disconnect the Power Optimizer from the string; it should remain connected to the PV module
Verify safe Power Optimizer voltage and current: max. 1V and 500mA
Connect the Power Optimizer’s positive and negative output connectors to the branch cable
Connect the positive probe of the insulation tester to the branch cable.
Connect the negative probe of the insulation tester to a ground point.
Select 500V testing on the insulation tester and measure the resistance.
Step 7
Power Optimizer and Module Results
If the measured resistance is 200MΩ or more, the Power Optimizer and module are not faulty.
If the measured value is less than 200MΩ, the Power Optimizer, the module or both are faulty. Continue checking as detailed in the following steps in order to know which one is faulty:
Find whether the leakage is from the module or from the Power Optimizer. Test each component individually by measuring the resistance between negative wires and ground:
Step 8
Testing the Power Optimizer
Disconnect the module from the Power Optimizer
Connect the power optimizer’s positive and negative output connectors to the branch cable
Connect the positive probe of the insulation tester to the branch cable
Connect the negative probe of the insulation tester to the power optimizer frame (ground point)
Select 500V testing on the insulation tester
Measure the resistance.
Step 9
Power Optimizer Test Results
If the value is 200MΩ or more – the Power Optimizer is fine, but the module is faulty.
If the value is less than 200MΩ, replace the Power Optimizer and test the module in case it is also faulty, as described in the next step.
Step 10
Connect the Module
Disconnect the branch cable from the power optimizer and connect it to the module:
Step 11
Test results
Measure the resistance:
If the value is with 40MΩ*m2 or more – the module is OK.
If the value is less than 40MΩ*m2, the module is faulty.
The typical value is 80MΩ for each module.
Replace the faulty component(s) as determined by the troubleshooting process.