Occupancy & Means of Egress
Occupancy Separation
Occupant Load Summary
Keynotes
Occupancy Legend
Legend
Sheet Notes
Key Plan
Refer to the ‘How-To’ sheet located at the top of this page, following the project examples.
Creating the View:
Create a new Area Plan, not a floor plan.
Choose the Life Safety Plan type when prompted.
Ensure all levels in the project have a Life Safety Plan view (no SIM. levels)
Area Boundaries:
Do not auto-generate boundaries — draw them manually based on program use (ie, AC or NON-AC, occupancy, etc.)
Assign each room/space the proper Occupancy Type per FBC.
Use Tagged Areas to show Net Area; avoid using filled regions.
Set Occupancy Classification and Net Factor as required.
Paths of Travel:
Use the RAILING family to draw travel paths.
Apply path-type filters for clarity.
Use Smart Tags for Travel Distances (do not use static text).
Confirm:
Distance auto-updates with path changes.
Worst-case travel path is shown.
Distance is taken from unit to corridor, not just the door.
NFPA rules apply for Entry/Exit door to corridor.
Indicate dimensions at dead ends and show minimum allowed.
Dimensions:
Use the F… dimension type.
The lowest allowable fraction (e.g., 1/8") for legibility has been setup in the template; this should not be adjusted
Tags & Room Names:
Use Smart Room Tags only. When tagging units, only include what type of unit (A1, B1-E, B1, etc.) - do not include "Unit" in the label
Avoid overlapping tags with paths, walls, or dimensions.
If tag is covered by furniture, relocate or flip the tag.
Furniture should only be turned on for public areas (ie, Clubhouses, lobbies at apartment buildings, amenities, etc.) - not in the apartments
Graphics & Visuals:
Use Detail Lines for fire ratings
Use Pick Line to lock fire-rated walls
Lock lines if the model shifts
Adjust linework as needed — especially at transitions
Every Life Safety Sheet must include Sheet Notes, Keynotes, Key Plan, Legend
Each sheet in the drawing set will include preloaded Sheet Notes that have been reviewed and approved by the firm’s Principals and Studio Directors. These notes are critical for documentation consistency and should not be modified without principal-level approval.
Usage Guidelines:
Do not add, remove, or revise Sheet Notes unless explicitly instructed by a Principal. Sheet Notes are considered locked content and are only updated at the firm-wide level after internal QA/QC review. Before issuing a set for internal QC, always verify that the Sheet Notes are the most current version.
How to Review for Accuracy:
Cross-check the notes on your sheet against the current keynote / sheet note reference file:
T:\1.Interim\0000-Keynotes-FAID.txt
All discrepancies must be communicated to Jeff Suchan and will follow the internal approval flow:
Office → PM/SD → Jeff Suchan → Design Technology → Back to Office
Important Reminder:
Do not copy/paste notes from other projects — always pull from the preloaded template.
This guide outlines the firm’s preferred method for creating reusable, clean key plans using a Generic Model Family, rather than a drafting view. This method improves consistency, allows visibility control, and avoids having to redraw the key plan on each sheet.
Start a New Family
Open a new Generic Model Family template (Generic Model.rft)
This will serve as your base key plan element, used across all applicable sheets.
Create a Diagram of the Building
In your active project model, create a loose diagram of the overall building footprint using Detail Lines.
Accuracy is not critical — this is a diagram, not a technical drawing. No dimensions will be shown.
Include major parts of the building (e.g., Part A / B or 1 / 2), not every wall or window.
Copy the Diagram into the Family
Copy and paste the detail lines from your project into the Generic Model Family.
Add Text Labels directly into the family to identify each portion of the building (e.g., “Part A,” “Part B”).
Create Filled Regions
Use Filled Regions to shade each building part.
Apply solid fills (grey) to match the firm’s visual standards for key plans.
Add Visibility Parameters
Assign each filled region its own Instance-Based Yes/No Visibility Parameter (e.g., Show_Part_A, Show_Part_B).
These will allow you to turn each part of the building on/off per sheet in the project.
Note: For Life Safety sheets, do not toggle these off — the full building must remain visible.
Load the Family into Your Project
Save the family with a clear name (e.g., KeyPlan_Generic_FAID).
Load it into your Revit project and place it in the bottom right corner of each sheet, adjacent to the sheet number.
Adjust Visibility Per Sheet
For all sheets except Life Safety, you may use the visibility parameters to highlight only the portion relevant to the sheet.
For Life Safety Sheets, leave all building parts visible — this ensures code reviewers see the entire project layout. It is also a Forum Standard that in Life Safety, the entire floor plan is shown.
On every floor of a structure, there will be a Unit for every Exit. That Unit is selected with a calculated distance determined by the building's shape, size, and possible fire sprinkler use. These Units will be used to calculate egress. For these Units only, three egress paths will be provided.
The first is the FBC (Florida Building code), where the travel path's start point is the Unit's farthest point from the unit exit door to the lowest level of the building's corresponding Exit.
The second and third are for NFPA ( National Fire Protection Association). The first of the two NFPA paths is within the Unit, where the start point of the travel path is the farthest point in the Unit from the unit exit door. The second NFPA path is from the Unit Exit door to the lowest level of the building's corresponding Exit.
FBC and NFPA paths are not to overlap.
View Filter - Filter for Railings, Type Name = Egress Path of Travel, Lines = Dash 3/32", Weight = 5
...
The F.SPEQ.Fire Extinguisher.Cabinet.Wall Revit family is designed to provide clear, well-oriented fire extinguisher cabinet placements across different plan types. It includes multiple types to ensure proper orientation and readability of fire extinguisher symbols, accommodating both Life Safety Plans (A1.11) and Floor Plans (A5.11).
F.Recessed.Floor Plan.Bottom
F.Recessed.Floor Plan.Top
F.Recessed.Life Safety.Bottom
F.Recessed.Life Safety.Top
F.Semi-Recessed.Floor Plan.Bottom
F.Semi-Recessed.Floor Plan.Top
F.Semi-Recessed.Life Safety.Bottom
F.Semi-Recessed.Life Safety.Top
F.Surface.Floor Plan.Bottom
F.Surface.Floor Plan.Top
F.Surface.Life Safety.Bottom
F.Surface.Life Safety.Top
Each type follows a structured naming system based on the following criteria:
Recessed, Semi-Recessed, or Surface: Determines how far the cabinet is embedded into the wall.
Recessed: Fully set into the wall.
Semi-Recessed: Partially embedded into the wall.
Surface: Mounted directly on the wall surface.
Plan Type:
To distinguish between plan types, two different 3D model text symbols are used for fire extinguishers:
Life Safety Plans (e.g., A1.11): Use a larger 3D model text symbol with a circle for enhanced visibility.
General Floor Plans (e.g., A5.11): Use a smaller 3D model text symbol without a circle for cleaner labeling.
To control which symbol is visible depending on the plan type, use the visibility of subcategories:
F.FE.Symbol.LifeSafety — Controls the circle symbol for life safety sheets.
F.FE.Symbol.Plan — Controls the smaller, standard symbol for general floor plans.
The multiple types within this family allow for:
Proper Symbol Orientation – Ensures readability of FE symbols regardless of placement (top or bottom of the wall in plan).
Clear Fire Extinguisher Identification – Differentiates between Floor Plan and Life Safety symbols for improved plan review.
Flexible Wall Integration – Provides Recessed, Semi-Recessed, and Surface-mounted options to match project design needs.
If a recessed FE cabinet needs to be placed on the bottom side of a wall in a Life Safety Plan, select F.Recessed.Life Safety.Bottom. This ensures:
The Life Safety FE symbol is displayed.
The text is oriented correctly (not upside down).
FL NFPA 1, 13.6.3.1.3.8.1 ('23)
Fire extinguishers having a gross weight not exceeding 40 lb (18.14 kg) shall be installed so that the top of the fire extinguisher is not more than 5 ft (1.53 m) above the floor. [10:6.1.3.8.1]
FL NFPA 1, 13.6.3.1.3.8.2 ('23)
Fire extinguishers having a gross weight greater than 40 lb (18.14 kg) (except wheeled types) shall be installed so that the top of the fire extinguisher is not more than 31/2 ft (1.07 m) above the floor. [10:6.1.3.8.2]
ADA ACCESSIBLE REACH REQUIREMENTS
308.3.1 Unobstructed. Where a clear floor or ground space allows a parallel approach to an element and the side reach is unobstructed, the high side reach shall be 48 inches (1220 mm) maximum and the low side reach shall be 15 inches (380 mm) minimum above the finish floor or ground.
The F.SPEQ.Fire Extinguisher.Cabinet.Wall family was designed to accommodate the largest fire extinguisher specified by Amerex: the Amerex Purple K Dry Chemical 796 Extinguisher. This extinguisher measures 26.5 inches in height, 11 inches in width, and 8 inches in depth, with a total weight of 56 lbs.
By designing the cabinet to fit the largest possible extinguisher, we ensure that it can be installed at a compliant height for all extinguisher sizes. This approach guarantees that any extinguisher used in a project will be positioned at the correct and accessible height.
Extinguisher Dimensions:
Model: Z Series Amerex Purple K 796
Height: 26.5 inches
Weight: 56 lbs (more than 40 lbs)
Relevant Code Requirements:
FL NFPA 1, 13.6.3.1.3.8.2 ('23)
For extinguishers over 40 lbs, the top cannot exceed 42 inches (3' 6") above the floor.
ADA Accessible Reach Requirements (308.3.1 Unobstructed)
The lowest point must be at least 15 inches above the floor.
Proposed Placement:
To ensure compliance with both NFPA and ADA while allowing a 1/4-inch buffer from both the top and bottom limits:
Top of the extinguisher is placed at 3' 5 3/4" (41.75 inches), ensuring it stays within the NFPA height limit.
Bottom of the extinguisher is at 15 1/4 inches, keeping it above the ADA minimum.
Final Placement Range:
Top of extinguisher: 41.75 inches (3' 5 3/4") (1/4" below NFPA max).
Bottom of extinguisher: 15.25 inches (15 1/4") (1/4" above ADA min).
This precise placement ensures the extinguisher meets both NFPA height limits and ADA accessibility requirements while allowing a margin for installation tolerance.
This graphic illustrates the code-compliant placement zone for the Amerex Purple K 796 fire extinguisher within a wall-mounted cabinet. The diagram is based on the NFPA 1 (2023) and ADA accessibility requirements discussed earlier.
Key Elements of the Graphic:
"No Placement Zone" (Red Area) – Non-Compliant Heights:
The top red section represents heights above 42 inches, which exceed the NFPA limit for extinguishers over 40 lbs.
The bottom red section represents heights below 15 inches, which would violate ADA's minimum reach requirement.
"Placement Zone" (Green Area) – Code-Compliant Heights:
This is the only allowable range for the extinguisher to ensure compliance.
The top of the extinguisher must be at or below 42 inches
The bottom of the extinguisher must be at or above 15 inches
"Amerex Purple K 796" (Teal Section) – Extinguisher Dimensions:
This section represents the extinguisher’s 26.5-inch height within the compliant placement zone.
It is centered within the green "Placement Zone" to leave a 1/4-inch margin from both the upper and lower code limits.
Fire Extinguisher Cabinet (White & Blue Object in Center):
The cabinet is positioned to enclose the extinguisher while ensuring the entire unit remains in the compliant height range.
While the cabinet itself is not directly regulated by height codes, its installation must ensure that the extinguisher inside is correctly positioned.
Ensures NFPA regulations for extinguishers over 40 lbs.
Meets ADA accessible reach requirements.
Provides a visual guide to prevent misplacement of the cabinet.
Leaves a slight 1/4" buffer on either side for installation tolerance.
This and similar schedules may be found in the A1.11 - Life Safety Plan
Story: Manually adjusted. FIRST FLOOR, SECOND FLOOR, ect.
Area: Manually adjusted. Space where the extinguisher is located.
Floor Area To Be Protected (SF): Manually adjusted.
Fire Extinguisher Size & Rating: Manually adjusted. Typical Set but Verify.
Max Area Of Protection Per Unit (SF): Manually adjusted.
Min. Number Of Extinguishers Per Floor Area: Manually adjusted.
Floor Area To Be Protected (SF) / Max Area Of Protection Per Unit (SF)= Value Rounded Up To Nearest Integer
Travel Distance (LF): Typical Set but Verify.
Provided Number Of Extinguishers: Manually adjusted. May be more than Min.
F.SPEQ.Fire Extinguisher.Cabinet.Wall
F.Tag.Area.Occupant Load
Occupant Load Tag - Click for more information
F.Tag.GANN.Occupant Exit.Non Parametric
Occupant Load Tag (Non Parametric) - Click for more information
F.Tag.Railing.Travel Distance
Travel Distance Tag - Click for more information
F.Tag.Model Group.Type Name
Model Group Tag - Click for more information
F.Tag.RVTLink.Type Mark
RVT Link Tag - Click for more information
F.Tag.GANN.Fire Extinguisher.Non Parametric
Fire Extinguisher Tag - Click for more information
To turn off walls in the FE symbol, go to VG and uncheck walls for the specific Legend view.
This could work in certain situations, but in instances where multiple Legend Components have walls, turning off all of the walls may not be desired.