SWS Detail: 6.0202.1 Local Ventilation: Clothes Dryer
Author: Brenna
Dryer vent material is vinyl and terminating into a unapproved location.
Dryer vent of rigid metal, properly sealed and supported discharging to an exterior approved location.
Remove any vinyl and plastic venting. Remove any damaged, crushed, or punctured venting.
Remove any lint buildup at dryer exhaust port and dryer lint trap.
Only a 4" rigid metal duct shall be used for dryer exhaust.
Do not use plastic or metal foil venting.
Follow work order to vent dryer to the exterior with shortest, most direct path.
Dryer exhaust duct must not exceed 35' in equivalent length unless fan assisted.
Deduct 5' for each 90 degree elbow and 2.5' for every 45 degree elbow from allowable length.
An existing termination may be used if it meet manufacturer's requirements.
Do not terminate duct into floor cavity, ceiling cavity, crawlspaces or attics.
Termination should be at least 3' away from intake openings and windows.
Duct must terminate at least 12" above finished grade, and 12" away from inside corners of the building.
Duct termination shall not be covered by porches or decks.
Connect duct with male fittings following directional flow of air towards termination to avoid build up of lint.
DO NOT PUNCTURE duct, DO NOT USE SCREWS
All exhaust duct must be supported every 4' to avoid sagging or any areas where lint may get trapped
A listed flex connector may be used as a transition to connect the dryer to the duct work.
Connector can not exceed 8' linear and can not be concealed within construction.
If exhaust duct runs through an unconditioned space, ductwork shall be insulated with a minimum of R-8 to prevent condensation
Exhaust terminations shall be in accordance to manufacturer's instructions.
Exhaust duct terminations shall be equipped with a backdraft damper.
Screens shall not be installed at the duct termination.
After securing housing for duct termination to outside of home, caulk around the termination to prevent air and water leaks.
Seal all duct connections with 181B or 181B-M listed material
DO NOT PUNCTURE PIPE, DO NOT USE SCREWS. This will cause lint to accumulate and become a fire hazard
Conduct a Worst Case draft test to verify Category I, II, and III appliances are venting safely before leaving home for the day.
Testing shall be recorded using the Utah WAP Worst Case Draft Test form.