Attic Ventilation

Desired Outcome:

Ensure vents meet proper performance characteristic for location and roof type

SWS Detail: 4.1088.2 Unconditioned Attic Ventilation

Author: Burl Kinoshita

Before

Unventilated Attic

After

Attic Roof Ventilation

Steps

  1. Roof vent

  • Follow steps 2 - 3b as applicable to roofing type.

2. Asphalt roofing

  • Steps 2a - 2g

2a. Positioning vents

  • Position vents evenly across roof, below the ridgeline so that vents can only be seen from one side of the home,

  • The top of the vent should be between 1 and 2 feet below ridgeline.

  • Ensure that vents are positioned so that you will not be drilling through any rafters.

2b. Pilot hole

  • Drill pilot hole near the center of each vent.

2c. Outline opening

  • Follow manufacture instructions to determine the size of the diameter opening.

  • Mark outline of the opening.

2d. Cut hole

  • From the exterior, cut out the hole for the vent.

  • Take care not to cut any structural members or plumbing or electrical lines.

2e. Pry and trim shingles

  • Gently pry up and break shingle tab seals around the top half of the hole

  • Trim shingles to allow for the installation of roof vent flashing.

  • Verify fit

2f. Install vent

  • Place roofing sealant on bottom of the flashing

  • Tuck the roof vents upper flashing under the two upper rows of shingles and slide into place

  • leave the bottom of termination flashing on top of shingles

  • Secure to roof using 4 or more roofing fasteners. Top fasteners should be installed under shingles.

2g. Seal vent

  • Use sealant to adhere shingles to the top of the vent flashing and to fasten them back to the roofing.

  • Cover nail heads with roof sealant.

3. Metal roofing

  • Follow Steps 2a - 2c and 3a - 3c where applicable

  • Wherever possible avoid adding ventilation to metal roofing.

3a. Install vent

  • Lay a bead of silicone down and place malleable flashing around vent

3b. Seal termination

  • Secure with screws every 1" and silicone around edge.

4. Soffit vents

  • Follow Steps 4a - 4e


4a. Install baffles

  • Move insulation away from soffit where soffit vent will be installed.

  • Install baffles to prevent insulation from falling on top of vent and prevent wind-washing.

  • Baffles should extend upward along the rafter to at least 4 inches above the finished insulation level.

4b. Outline opening

  • Measure and draw opening for soffit vent.

  • Opening measurements must be at least 1 inch smaller than the vent size.

4c. Cutting hole

  • Cut and remove soffit on inside measurements.

4d. Apply sealant

  • Apply a bead of appropriate sealant around edge of this opening you have cut.

4e. Securing vent

  • Fasten soffit vent using nails or screws.

5. Gable vent:

  • Follow steps 5a - 5f

5a. Identify vocation

  • Follow instructions in work order and Identify where to install the vent on gable.

  • Note the location of structural members, and plumbing and electrical lines.

5b. Trace hole

  • Locate where to install the vent on the exterior of the home and trace outline of duct avoiding structural members and utilities.

5c. Cut hole

  • Determine vent diameter and cut hole in exterior wall slightly larger, but not more than 1/4" larger, than the outer diameter of the vent shroud on the termination.

  • Take care not to cut any plumbing or electrical lines.

5d. Install flashing

  • Whenever possible, install flashing under cladding

5e. Install vent

  • Position vent termination flush against exterior. Orient to allow damper(s) to close when not in use.

  • Secure to house using 4 or more exterior grade fasteners

5f. Seal termination

  • Seal gap between termination and exterior of home with exterior grade caulk to prevent water intrusion.

Notice: Screen

  • Vents must have screens, with 1/4 to 1/16 inch opening.

  • This is to help prevent pests, snow and rain entering through the vents.

  • Vertical vents must have louvers to deflect rain.

Attic Ventilation Standard

  • Adjustments to attic ventilation shall meet the current requirements of the IRC.

  • The IRC requires that the minimum net free ventilating area shall be 1/150 of the area of the vented space.

  • EXCEPTION: If you have equal parts high and low ventilation area shall be 1/300 of the vented space.

  • Attic vent types will be made of corrosion-resistant material for their specific locations.

  • Powered attic ventilator will not be used.