SWS Detail: 4.0102.3 Inaccessible Ceilings - Dense Pack; 4.0103.6 Accessible Attic - Dense Pack Insulation; 4.0104.1 Knee Wall - Dense Packing; 4.0201.3 Accessible Walls Dense Pack Insulation; 4.0202.1 Enclosed Walls Dense Pack Insulation; 4.0301.4 Dense Pack in Joisted Cavities With Rigid Barrier; 4.0302.3 Exposed Floors Dense Pack with Rigid Barrier
Author: Brenna Dunn
Missing insulation along the top of each cavity
Continuous insulation in the wall
Review work orders to determine if Lead Safe RRP is required.
When required, follow RRP guidance as listed in the Lead Safe work section of this field guide.
Depending on the location of the work you will need to work with the client to:
Clear furniture and belongings away from exterior walls.
Use drop cloths and other measures to protect the client's belongings.
Move obstructions around the outside of the home as need for access.
Look for any hidden holes or openings in cavity (e.g. behind posters hanging on the wall).
Drywall must be a minimum thickness of 1/2" for 16" framing, or 5/8" for 24" framing.
Panels must be able to support the weight of dense pack.
Surface material shall cover 100% of the cavity.
If major repair is needed, coordinate with auditor to see if incidental repairs can be justified.
Steps 4a -4f are examples of how to access the various types of walls you will be insulating.
Drill a 2 1/2" diameter hole near center of wall cavity.
One hole may be acceptable to fill an entire space if fire blocking or other obstructions are not in the cavity.
Drill a 2 1/2" hole at the top third and lower third in each wall cavity.
Chalk a line at chair rail height.
Drill the 2 1/2" holes along the chalk line.
Once the wall is insulated install foam plugs in holes.
Install chair rail molding over holes.
Caulk on top and bottom of chair rail.
Remove one row of siding that runs the full length of the wall for access to exterior sheeting.
Drill a 2 1/2" hole between each wall cavity.
Install blocking at the bottom and top of wall cavities.
Send fill tube down the wall cavity from inside attic when possible.
Otherwise block both the top and bottom of each wall cavity and do a standard drill and fill.
Staple netting to studs or joists with 1/2" crown staples no more than 2" apart.
Use an infrared camera, See-snake, plumbers tape or other method to verify if the wall has blocking in it.
Fill cavity to achieve manufacturers specified density.
With machine turned off, insert fill tube until it reaches the end of the cavity, then pull back a few inches.
Start material fill.
Pull back the fill tube approximately 1' when material is no longer moving and repeat process until there is only approximately 6" of tubing remaining in the wall cavity.
Using method above probe the fill tube into different areas of the cavity and use multiple angles to fill the cavity with as much material as possible.
Sheetrock walls: place a foam plug in the hole and finish with one coat of sheet rock mud.
Paneling or exterior walls: Caulk a plastic plug in place and re-attach any siding removed.
Conduct a Worst Case Draft (WCD) test to verify Category I, II, and III appliances are venting safely before leaving home for the day.
Testing shall be recorded using the Utah WAP Worst Case Draft Test form.
A dated insulation certificate signed by the installer will be posted on a wall in the space where the furnace is located, a utility room or an approved location inside the building.
Certificate shall include:
Installed insulation type
Coverage area
Installed thickness and minimum settled thickness.
Number of bags installed in accordance with manufacturer specifications.