SWS Detail: 5.0109.3 Evaporators; 5.0109.1 Condensers; 5.0102.1 Condensate Removal; 5.0109.2 Air Handlers
Author: Jesse
Pull off front cover of AC coil, slightly lift up high enough that the underside of the coil can be inspected with a camera or mirror.
If needed use a bristle attachment on a vacuum or a commercial foam cleaner and clean any buildup off the under side of the coil.
Inspect and clean the condensate pan and drain lines as needed to ensure the condensation can flow freely.
Check the condenser for build-up on the exterior side.
If there is build up, remove the outer casing if needed, gently rinse off what you can with a low-pressure pump sprayer that has an AC Coil cleaning agent in it, or a hose after applying a foaming cleaning agent.
Do not apply high water pressure as this will cause some build-up to be pushed further into the fins of the condenser or could bend the over. Straighten any bent fins with a fin comb.
Check all lineset for kinks or leaks & check insulation for dry rot, rips or missing sections.
Replace any sections that are not adequate.
Lineset's exposed to sunlight shall be protected from UV degradation.
Verify fan speed setting are to manufacturer specification.
Check that static pressure is within manufacturer specifications
Check the 𝚫-T. The 𝚫-T should be between 17-20⁰.
Use a multi-meter to check that the capacitor is within the range specified on its data label.
Use a multi-meter to check that the fan amp draw is within the specifications listed on its data label.
Use a multi-meter to check the compressor amp draw and compare it with the manufacturer specifications for both Rated Load Amps (RLA) and the Locked Rotor Amps (LRA).
Only consider charging if the 𝚫-T or compressor amperage are not within manufacturer specifications after all AC components are clean, insulated and the condenser fan amperage and duct static pressures are within range.
You only ever hook up your gauges when necessary. Doing so when not needed may cause loss of refrigerant or unwanted air or contaminants into the system.
Complete the A/C Start Up and Performance Checklist
Only EPA-608 Universal or Type II Certified individuals are allowed to perform this measure.
All equipment must be charged to manufacturer specifications.