SWS Detail: 5.0106.1 General Duct Sealing; 5.0107.1 General Duct Insulation
Author: Brenna Dunn
Duct boot is not properly supported and is disconnected from floor. Ductwork is uninsulated
Ductwork is secured to the floor of the conditioned space, insulation has full coverage and all seams are taped.
Existing insulation outside of the thermal boundary must be a minimum of R-8 and have consistent coverage of all ducts.
Any ductwork exposed to the exterior must have a minimum insulation of R-12.
Insulated flex duct is acceptable when in good condition.
Damaged or wet insulation shall be removed and disposed of.
NOTE: If any of the above conditions are identified and not on the Work Order or Energy Audit contact Supervisor and discuss issue prior to proceeding.
Select insulation with a flame spread and smoke development index of 25/50 when tested in accordance with ASTM E84 or UL 723.
Select insulation that includes an exterior vapor retarder layer.
Follow the manufacturer's specifications to determine the correct placement of the reflective layer or vapor barrier of insulation.
See the Air Seal Duct section of this field guide.
Install all duct air sealing measures listed in the work orders before installing insulation.
If duct sealing is not listed on work order, discuss installation with auditor before installing insulation.
Wrap duct with duct wrap or fiberglass blanket. Duct insulation should be a minimum of R-value as noted in Step 1.
Insulation should have full coverage and be consistently contacting duct with minimal to no sagging.
Vapor barrier will be facing outwards, not towards the interior of wrapping.
Insulation shall be durably fastened using mechanical fasteners such as stick pins, screws and washers, plumber straps, or wire.
Avoid compressing the insulation as much as possible.
All seams of insulation must be taped with UL 181 approved tape.
Tape in a way that prevents gapping of insulation and allows for continuous insulation.
A dated insulation certificate signed by the installer will be posted on a wall in the space where the furnace is located, a utility room or an approved location inside the building.