Charge the battery for at least 12 hours before installation. A minimum of 1 hour of charge is required before running any tests.
Choose the diagram that matches your fixture:
Diagram 1 — Fixture under 50W with no dimming
Diagram 2 — Fixture under 320W with 0–10V dimming active
Diagram 3 — Fixture under 320W with 0–10V dimming capability but not in use
For all diagrams, connect the AC input wires first (Black/Red L1, White Common, Black L2), then connect the output wires to the luminaire. Always connect the Battery Connector last.
If a switched L2 line is not used, combine the L1 and L2 lines together. Pink, Gray, Pink/Orange, and Gray/Orange dimming wires are interchangeable.
Plug the USB-C end of the Connector Cable into the Hexmodal Controller
Plug the RJ12 end into the RJ12 slot on the microinverter
Press and hold the button on the Controller for 6 seconds until the LED blinks green — the device will join the network within 1–2 minutes
Secure the Controller to the microinverter using the provided double-sided adhesive
Scan the QR code on the Hexmodal Controller with your phone
Enter the location information and tap Save and Submit
Tap Run Test in the Hexmodal app
Select Run 60 Sec Test
Wait for results — the screen should confirm "In Compliance. Completed This Month's Testing"
Thread the white Test LED cable through the luminaire's access port so it's visible from the outside (drill a small hole if needed)
Apply the QR sticker to the outside of the luminaire in a visible spot
Confirm before you finish:
✅ QR sticker is attached and visible
✅ Test LED is visible from outside the luminaire