A143

An experimental study of bioaerosol (1-10 um) deposition in a ventilated chamber

Brief:

Understanding of bioaerosols deposition in ventilated environments can significantly improve our current knowledge on exposure. This study presents an experimental and numerical analysis for bioaerosol deposition in a scaled ventilation chamber. Three different group sizes of common indoor airborne bioaersols ranging from 1 to 10 μm, (Micrococcus luteus, Staphylococcus aureus), (Aspergillus niger, Penicillium citrinum) and (Rhizopus sp.), were atomized and injected to a small chamber with three controllable ventilation flow rates varying from 1.7 h−1 to 18.8 h−1. Twenty-eight (7 × 4) Petri dishes were placed at the bottom of the chamber and deposition was counted after inoculation. A commercial computational fluid dynamics tool was used to predict bioaerosol deposition. The results were compared with experiments and satisfactory agreements between them were observed. The results reveal that the larger the aerosol size, the shorter the deposition distance away from the inlet. The comparisons are further improved if non-spherical shape factor is considered.

Further Information:

Lai ACK, Wong LT, Mui KW, Chan WY, Yu HC, 2012. An experimental study of bioaerosol (1-10 um) deposition in a ventilated chamber, Building and Environment 56 118-126.