Active water leaks, fuel leaks (i.e., gas, oil, propane), and pest intrusions
Uncovered electrical junctions
Improperly terminated devices (ventilation fans, dryers, plumbing stacks, condensate lines, combustion appliance flues/chimneys, etc.)
Unshielded high-temperature devices (non-IC rated recessed lights, chimneys, flues, vents, etc.) unless they are zero clearance devices
Insulation escape openings
Verify that installation area is:
Intact and able to support insulation weight
Air and duct sealing is complete
Verify that all plumbing is within the thermal boundary, or insulated appropriately
Intact and able to support insulation weight
Air and duct sealing is complete
Verify that all plumbing is within the thermal boundary, or insulated appropriately
Choose appropriate option from steps 3a - 3b to patch mobile home belly
To patch a flexible belly, use both adhesives and stitch staples to bind the flexible patch to the flexible belly material.
In weaker areas of the belly screw wood lath to the framing to reinforce belly material.
Use belly fabric or house wrap to cover damaged area. Creating a "new" belly.
Secure edges of fabric by rolling a 1x2 into the edges and securing the 1x2 to framing members of trailer with appropriate fasteners.
Tape any seams with manufacturer approved tape AFTER properly preparing surface to ensure adhesion.
There are two methods for installing loose fill fiberglass insulation in a mobile home belly
Blow in fiberglass through belly material; steps 5-5a
Blow in fiberglass through rim; steps 6 - 6e.
Pick the most appropriate method for the job you are working on.
Loose fill fiberglass is the only material to be used in WAP
Cut a hole in the belly material just big enough to fit the insulation hose through it
Using the insulation hose fill the cavity taking care not to over pressurize and cause a blowout
After insulating the belly patch the access hole with both adhesives and stitch staples to bind the flexible patch to the flexible belly material.
Loose fill fiberglass is the only material to be used in WAP
Follow steps 5a-5e to install blown in fiberglass in the mobile home belly
Remove skirting to gain access to the rim joist.
Use caution older sun damaged skirting can become brittle.
Drill hole big enough to fit fill tube.
Fill cavity to manufacture specified density for the material being used.
Watch belly material and repairs for blow outs.
Best practice would be to go inside the home and verify ducts were not breached with insulation materials.
Conduct a Worst Case draft test to verify Category I, II and III appliances are venting safely before leaving home for the day.
Testing shall be recorded using the WAP Worst Case Draft Test form.
A dated insulation certificate signed by the installer will be attached in the interior electrical panel or other approved location.
Certificate shall include: Insulation Type, Coverage Area, installed thickness and minimum settled thickness, Number of bags installed in accordance with manufacturer specifications