SWS Detail: 7.0301.2 Tank Insulation
No water heater blanket
Properly installed water heater blanket
Minimum R-Value of R-10.
Has a flame spread of 25/450 or less when tested in accordance with ASTM E84 or UL 723.
Clearly labeled with R-Value
Cut and fit blanket to allow for maximum continuous insulation of tank.
Fold the top 4" of the insulation blanket down so top edge will be finished with vinyl facing.
Leave insulation exposed at bottom to allow insulation to dry.
For ELECTRIC water heaters ensure you cover top of tank with insulation.
For gas water heaters DO NOT cover top of tank, this can obstruct the draft diverter.
Maintain a minimum of 2 inches away from gas valve and burner access panel. DO NOT install insulation below burner access panel.
Maintain a minimum clearance of 6" between combustible tank insulation and fuel-fired water heater draft hood and/or single wall metal vent materials
Do not wrap the top of fuel-fired water heaters or cover combustion air intakes
Do NOT cover the pressure temperature relief valve or discharge line with insulation.
IF relief valve exist but no discharge line. Install discharge line outside the insulation within 6 inches of the floor
For ELECTRIC water heaters mark insulation to locate thermostat and heating element access panel.
Cut bottom and sides but NOT the top. This will create a hinge that allows access to these panels
Use tape to create a finished edge leaving no exposed insulation.
Install nylon straps (like zip-ties) over the insulation within 6 inches of the top and bottom and one in the middle of the tank with minimal compression.