See bluprint page 103 for HVAC layout
Image 6
5" nail guard plates are installed for all HVAC/Electrical/Plumbing lines within 5" of top or bottom plates
Image 2
Ridged barrier is in place where ever the trunk line transitions between floors.
This image is a place holder.
Image 3
Secure all HVAC lines with straps as per code
Image 4
Thermostat is located between the studs adjacent to the pantry.
This image is a place holder.
Image 5
Thermostat located to the left of stairwell while looking at the stairs.
This image is a place holder.
Image 7
Drain pan is installed end to end underneath the furnace in the attic
Image 8
Drain pan float switch must be installed and turned the right way (into the drain pan)
This image is a place holder.
Structural mending straps (Simpson Strong Ties) are required anywhere the top plate is cut more than 50% for line set
Image 9
Ensure that all floor transitions, including stairways, are properly fire caulked or foamed
Image 9
All HVAC penetrations through exterior walls must be fully sealed with silicone.
This image is a place holder.
Image 10
Location of outdoor unit cannot obstruct stair paths nor window visibility. Confirm with Super or PM about outdoor unit location.
This image is a place holder.
Image 11
Tape energy efficiency certificate to cabinet door under kitchen sink.
This image is a place holder.
Image
Ensure that face plate for white dryer vent is installed at trim out.