Refer to page 59 of the manual
Open the software
Open the emsiso CAN logger connected
Open the emdrive configurator
Going into network, go into connection
Refresh ports and open corresponding port to CAN logger
Go to nodes and scan and download node 1
Go into SDOBROWSER, set mode of operation to 9 or 10
Add corresponding slider
Add two shortcuts, one for control word set to 6 to turn it off and 15 to turn it on PWM
Go into PDO and right click any parameter you want to watch and add to watch
Once ready go into reset and set to operational then press control word 6 then control word 15
Go to SDOBROWSER and search for error codes in the error codes parameter
Can then take any values and the object values and convert it to hex and then go into the emdrive manual to find out the error code
Bit values can be read in the warning register which will tell you where the error is coming from, from the corresponding bit