COMMON QUESTIONS AND ANSWER


In ships, voltages upto and equal to 1000 volts is called as low voltage system and voltages above 1000 volts is called high voltage system. Normally low voltage system is common on board. But rising demand for power due to heavy consumers on new ships require an efficient and surplus power supply. The answer is high voltage system.

Why high voltage system used on ships ?

The following advantages of high voltage system explain why it is preferred over low voltage system.

  1. As we mentioned, higher power demand for heavy consumers on ships is the first reason to choose high voltage on ships. High power bow thruster electric motors, reefer containers in container ships, cargo cooling machineries in gas carriers, etc. are examples of such heavy power consumers.

  2. High voltage machineries have much reduced size and weight compared to same power low voltage counterpart.

  3. Reduced weight and space for machinery means increased space for cargo and more profit.

  4. Using electric propulsion further reduces engine room size, again more cargo space and profit.

  5. Ease of installation and reduced installation cost.

  6. Conductor size is reduced due to low current flow in high voltage system, means reduced copper requirement and low cost.

  7. In high voltage system, copper loss or I²R losses are much reduced when compared to low voltage system, as the current flow is less.

  8. Overall estimated 1/3 rd reduction in cost compared to low voltage system.

What are the disadvantages of high voltage system on ships ?

  1. Handling high voltage means high class insulation to be used on conductors. (Generally ‘F’ class and above)

  2. Higher voltages means greater risk and hence require stringent safety procedures.

  3. Skilled labour required for handling high voltage system.

  4. Danger of arcing, chances of arc flash and arc blast.

  5. Special switch gears are required to preventing arcing.

Why machinery working in high voltage system has reduced weight and size ?

Consider an electric motor consuming power of 500 kW

We have the power, P = √3 V I Cos ∅

In low voltage system, power, P = 500 x 1000 Watts, power factor, Cos ∅ = 0.8, Voltage, V = 440

P = √3 V I Cos ∅

Current, I = P / (√3 V Cos ∅)

I = 500000 / (√3 x 440 x 0.8 )

I = 820 Ampere

Similarly, In high voltage system, power, P = 500 x 1000 Watts, power factor, Cos ∅ = 0.8, Voltage, V = 3.3 kV

P = √3 V I Cos ∅

Current, I = P / (√3 V Cos ∅)

I = 500000 / (√3 x 3.3 x 1000 x 0.8 )

I = 109 Ampere

So for an electric motor, working in high voltage system draw very low current compared to that of low voltage system. As current carrying capacity of conductor reduces, size of the conductor can also be reduced much. This considerable reduction in conductor material result in reduced size of machinery and save space for installation.

Why copper loss and iron loss is less in high voltage system ?

From the above comparison on current flow between a high voltage system and low voltage system, it is clear that current draw with high voltage is much lesser. Hence copper loss or I²R losses and iron loss are considerably lesser.

What is meant by arcing, arc flash and arc blast in high voltage system ?

  • Arcing is the production of unintentional electric arc during opening circuit breaker, isolator or contactor due to the discharge of electricity through the medium between the two contacts. (In fact arcing occurs during closing the breaker also).

  • Arcing also occurs when heavy current flow to earth during an earth fault or short circuit fault due to insulation failure.

  • During arcing temperatures at the arc terminals can go upto 20000 ºC or more, which is around 4 times the temperature of sun’s surface.

  • The intense light formed at the point of arc is called as arc flash.

  • Instant heating of air surrounding the arc occurs and conductors vaporises, resulting in formation of a high pressure wave. If the pressure wave is not released, it results in an explosion called arc blast.

What are the hazards of arc flash and arc blast ?

  • Permanent damages to the electrical equipment.

  • Irreversible damage to the human tissue and incurable burns due to very high temperatures.

  • Arc flash produces intense UV light, resulting permanent or severe damages to the eye vision.

  • Pressure wave from the arc blast compresses the eyes, resulting permanent or severe damages to the eye vision.

  • Heavy noise (above 140 dB) may damage hearing ability, sudden pressure changes may rupture ear drums also.

  • Arc blast explodes the equipment, ejecting parts with tremendous force and velocity. This may result in damages to personnel and property.

  • Flammable materials present in the vicinity of arc may ignite, causing secondary fires.

What is the difference between short circuit and short circuit level ?

  • A short circuit is a fault which occurs when the current in a system deviates its normal path and start flowing through an alternate path.

  • Since the alternate path offers very low resistance, the current increases very much above the normal value.

  • Short circuit level (SCL) is the maximum possible current that flows through a circuit during a short circuit fault.

What is the effect of short circuit fault in high voltage system ?

  • High current flow during a short circuit fault result in increased temperatures, which damages insulation, produces high thermal and mechanical stresses in the system, may cause arcing, arc flash and arc blast.

What are the methods adopted to prevent ill effects of short circuit fault ?

  • Protective relay installed in the system immediately trips and isolates the equipment during a short circuit fault within a short time. This prevents the effects of high current flow through the circuit.

  • The generators, cables, equipment, switch gears, etc. associated with the system are designed to withstand the heavy current during short circuit fault for this short duration of time.

  • Importance of Insulation Resistance (IR)

The high voltage system consist of generators, cables for power distribution, transformers, switch gear, and consumers. Here, consumers are large electric motors for propulsion, air conditioning compressors, bow thrusters, etc. Insulation resistance is the key parameter which gives the general condition of an electrical equipment. First of all, make sure IR values are to be checked between phases and between phases and earth periodically. In addition, these IR values are recorded for future references. Also, high voltage equipments are normally designed for a useful insulation life of 20 years and more. Hence proper operation within rated power, temperature and timely maintenance ensure prolonged life of the equipment.

In high voltage system, insulation resistance is measured using a 5000 volt DC megger, for voltages upto 6.6 kV. Furthermore, insulation resistance is measured under following conditions.

  • Routines test as per planned maintenance system (PMS)

  • After a major repair of the equipment, and

  • Troubleshooting purposes

What is the procedure / precautions for measuring insulation resistance of a high voltage equipment ?

  • First of all, disconnect the power supply to the high voltage (HV) equipment by opening circuit breaker and opening isolator.

  • In addition, confirm that all the phases are dead using an approved live line tester. Also make sure to check the live line tester for proper functioning using the testing tool provided along with the same.

  • Close the earthing switch now and make sure all the conductors are earthed.

  • Now connect the insulation resistance (IR) tester to the conductor, with safety earth connection ON. This is to ensure that the operator is not in contact with any unearthed conductor during insulation resistance (IR) measurement.

  • After connecting insulation resistance (IR) tester to the circuit, safety earth is to be disconnected.

  • Now insulation resistance (IR) test is applied and recorded.

  • After completion of the testing, safety earth is to be reconnected.

  • Now disconnect the insulation resistance (IR) tester from the circuit.

  • This safety measure to be followed for each separate IR test.

Why normal insulation resistance (IR) values are unreliable for high voltage machinery ?

  • IR values taken for a machinery at different temperatures are unreliable, especially when the temperature difference is more than 10 °C.

  • Also for high voltage system, it takes to stabilise the IR values. So instantaneous readings may lead to false interpretations.

What is meant by Polarization Index (PI) ?

  • Polarization Index (PI) value is the ratio between the insulation resistance (IR) value measured after the application of the test voltage continuously for 10 minutes to the IR value measured after 1 minute of application.

  • PI = (IR value after 10 minutes) / (IR value after 1 minute)

  • PI readings are less sensitive to changes in temperatures.

  • It will take some time for leakage currents while IR testing to attain saturation, hence reading is taken after 10 minutes.

  • PI value of 2 or more is considered as satisfactory. If the PI value is less than 1.5, equipment to be used only after improving PI value.

  • An electronic merger tester is essential for PI test. Because hand driven merger testers will not be able to give the steady test voltage for long time.

Why it is necessary to measure bolted bus bar joint resistance ?

  • High current flows through the bus bar. Any resistance in the bus bar cause resistive heating (I²R heating).

  • Same situation is applicable for any joints in the circuit.

  • This resistive heating produces hot spots or over heated areas. It is unsafe and may gradually reduce useful life time of the equipment.

How to measure bolted bus bar joint resistance ?

  • A normal ohm meter only drives small milli ampere (mA) current through the circuit. So it is not desired for measuring bolted busbar joint resistance.

  • Special low resistance micro ohm meter (also known as ducter) is normally used for measurement.

  • A calibrated current is allowed to pass through the circuit (say 10 Amps). Also the voltage drop across the circuit is measured. Hence resistance can be measured from the formula, R = V / I

  • For a healthy bus bar, joint resistance is about few milli ohms (mΩ).

How the hot spots in the bus bars or surrounding area is checked ?

  • It is necessary to keep the system running live to analyse any hot spots.

  • A recording infra red camera can take thermal images of different parts of the system from a safe distance.

  • These thermal images are processed in a computer program to display hot spots and temperature variations.