Design of Reinforced Concrete Shear wall
Design of Reinforced Concrete load bearing shear wall
Situation: A reinforced concrete load bearing shear wall supporting for a 15 story building
Florida Building Code: 2010
Design code: ACI 318-05
Design data:
Vertical load: (service load)
Uniform factored Load ( DL +LL) = 210 PSF
Dead load at each floor and roof: PD = 217 kips
Live load at each floor and roof: PL = 133 kips
Wind shear force: (service load)
15th floor: V15 = 40 kips, ,
14 floor: V14 = 40 kips
13 floor: V13 = 40 kips
12 floor: V12 = 40 kips
11 floor: V11 = 39 kips
10 floor: V10 = 39 kips
9 floor: V9 = 38 kips
8 floor: V8 = 38 kips
7 floor: V7 = 37 kips
6 floor: V6 = 37 kips
5 floor: V5 = 37 kips
4 floor: V4 = 36 kips
3 floor: V3 = 34 kips
2 floor: V2 = 33 kips
1 floor: V1= 31 kips
Total Shear: 559 kips =Vu
Factored Shear ( 1.6 x 559 k= 894.4 kips)
Vu= 894.4 kips
Floor height: H = 10 ft
Length of wall: lw = 18 ft
Width of wall: h = 12 in
Concrete strength: fc' = 4000 psi
Yield strength of steel: fy = 60 ksi
Assumptions:
1. out-of-plan moment is negligible
2. The wall is an interior wall.
Requirement:
Design reinforcement for shear wall
Solution
Maximum shear occurs at load combination: 1.3D+1.6W+1.6L
Calculate maximum shear force at first floor;
Maximum factored shear: Vu = 40 kips
Check maximum shear strength permitted
Assume effective depth, d = 0.8 (18) = 14.4 ft ( 173 in)
Strength reduction factor, f = 0.75
fVc = 2 Ø Öfc' b d = 197 kips > 40 kips O.K.
Critical section for shear at smaller of 18 ft/2 = 9 ft , H/2 = 7.5 ft
Calculate factored overturning moment and weight of wall at critical section
Mu = = 59,473 ft-kips
Nu = = 350 kips
Calculate shear strength of concrete:
fVc = 0.75 [3.3 Öfc' b d + Nu d/ (4 lw)] = 314.2 kips
Mu/Vu - lw/2 = 57.5 ft
fVc = 0.75 { 0.6 Öfc' + lw ( 1.25 Öfc' + 0.2 [Nu/(lw* h)]) /( Mu/Vu - lw/2)} h d = 239.9 kips (Use)
Or fVc = 0.75 (2 Öfc' h d) = 197 kips
Design horizontal shear reinforcement:
Vs = Vu - fVc = 894.4- 239.9 = 654.5 kips
Use #4 bar in two layer, area of reinforcement, Av = 0.4 in2. (Code requires two layers for 12" wall)
Spacing: S = fAv fy d /Vs = 4.50 in
Check maximum spacing: (18x12)/5 = 43 in, 3 (10) = 30 in, or 18 in Use 18"
Check minimum reinforcement: rt = 0.4 in2 / (18x10) = 0.0019 < 0.003
Use rt =0.003, spacing S = 0.4 in2 / (0.003)(h) = 11.11 in Use 11 in
But As Built wall horizontal reinforcement found based on X Ray tests is #4 bars ( double) @ 4 inches o.c.
OK
Design vertical reinforcement
rl = 0.003 + 0.5 (2.5 - hw/ lw )( rt - 0.003) = 0.003
Use rl = 0.003
Use #4 bars in two layers at 4" O.C ( As Built)
Calculate factored moment and axial load at base:
Mu = 59,473 ft-kip
Nu = 350.0 kips
Design as a column subjected to axial load and bending
Gross area, Ag = (18)(12)(12) = 2592 in2.
Assume tension control section, f = 0.9
fNu/Ag = 0.122 ksi
fMu/(Ag lw) = 0.095 ksi
From ACI column design chart (See column design section), Area of reinforcement, r = 0.011
Area of reinforcement, As = (0.01)(18x12)(12) = 22.8 in2.
Use #10 bars, number of bar, n = 22.8/1.27 = 18 each
As Built: #11 bars @ 6 “ on center as checked by GC based on test holes. ( 18 each vertical bars per 4.50 ft section x 2 = 9 ft.
Use 18#11 bars at each end of shear wall, column ties is required since r > 0.01. Use #4 ties at 4" O.C.
Check Deflection at top of Shear Wall:
Deflection: wL4/8EI
W= 3,200 Lbs/Ft or 266.67 Lbs/In
L= 150 LF or 1800 Inch
I=
S=
2,985,984.00
41,472.00
I= 2,985,984 in4
E= 57,000 Sqrt (4000 psi)= 3,604,996
Δ= 32 inches at top of shear wall. ( worst case)
See Wall section attached.
See hand calculations attached for worst load combination analysis ( Dead and Wind Loads).
DISCLAIMER
THE INFORMATION ON THIS WEB PAGE IS NOT INTENDED TO BE COPIED, USED OR TRASNMITTED
TO ANY THIRD PARTY SINCE THIS INFORMATION IS SHOWN FOR ILLUSTRATION PURPOSES ONLY.
ANY COPYING, USE OR TRANSMISSION OF THIS OR ANY OTHER SECTIONS OF THIS WEB SITE IS
STRICTLY PROHIBITED.