START HERE — REQUIRED SEQUENCE
1. HPR-BL (Baseline — Part A)
2. NIRET (Authorization Gate)
3. HPR-BL (Part B — ONLY if authorized)
4. Intervention
5. HPR-V (Post Verification)
DO NOT SKIP STEPS
DO NOT CHANGE ORDER
Violation = ALL RESULTS INVALID
If you touch the system before baseline:
You are no longer measuring reality.
You are altering it.
HVAC PERFORMANCE RECORD — BASELINE (HPR-BL)
--------------------------------------------------
PURPOSE
--------------------------------------------------
This record establishes system reality BEFORE any intervention.
It is a measurement-only document used to preserve the
original operating condition of the system.
DO NOT:
- Diagnose
- Assign fault
- Recommend repairs
- Interpret results
Record only what the system is doing.
This record becomes the foundation for:
HPR-BL → NIRET → INTERVENTION → HPR-V
If this baseline is incomplete, altered, or violated:
NO diagnostic determination is valid.
--------------------------------------------------
INITIALIZATION
--------------------------------------------------
Date: ___________________________
Start Time: _____________________
Technician Name: ________________
System Location: ________________
System Type: ____________________
Equipment ID / Model: ___________
--------------------------------------------------
STEP 0 — SYSTEM VALIDITY GATE (ALL MUST PASS)
--------------------------------------------------
☐ Cooling mode active
☐ System ran ≥ 20 minutes (stabilized)
☐ Outdoor temperature within operating range
☐ Return air within normal range (~70–80°F)
☐ No visible icing, oil leaks, or electrical faults
☐ Airflow not restricted (filter, coil, vents checked)
📸 System Running Photo: __________________
IF ANY ITEM IS UNCHECKED:
BASELINE INVALID — STOP
==================================================
PART A — NON-INVASIVE BASELINE (REQUIRED)
==================================================
--------------------------------------------------
STEP 1 — TEMPERATURE MEASUREMENTS
--------------------------------------------------
OAT: ______ °F
RAT: ______ °F
SAT: ______ °F
SLT: ______ °F
LLT: ______ °F
📸 Temperature Readings: __________________
📸 Probe Placement: _______________________
--------------------------------------------------
STEP 2 — DERIVED VALUES
--------------------------------------------------
Air-Side Split (RAT − SAT): ______ °F
Liquid Line Approach (LLT − OAT): ______ °F
Suction Depression (RAT − SLT): ______ °F
--------------------------------------------------
STEP 3 — STABILITY VERIFICATION
--------------------------------------------------
T+0
OAT: ____ RAT: ____ SAT: ____
SLT: ____ LLT: ____
T+2
OAT: ____ RAT: ____ SAT: ____
SLT: ____ LLT: ____
T+5
OAT: ____ RAT: ____ SAT: ____
SLT: ____ LLT: ____
--------------------------------------------------
STABILITY CLASSIFICATION
--------------------------------------------------
☐ Stable
☐ Minor Drift
☐ Unstable
IF UNSTABLE:
DATA INVALID — RESTART
--------------------------------------------------
MANDATORY TRANSITION
--------------------------------------------------
You MUST now perform NIRET.
DO NOT:
- Connect gauges
- Measure pressure
- Access refrigerant
Failure to perform NIRET:
INVALIDATES this record.
==================================================
PART B — REFRIGERANT SIDE (LOCKED)
==================================================
ONLY COMPLETE IF NIRET = GO
Suction Pressure: ______
Head Pressure: ______
Superheat: ______
Subcooling: ______
📸 Gauge Readings: __________________
--------------------------------------------------
INTEGRITY RULE
--------------------------------------------------
If Part B is completed without NIRET:
THIS RECORD IS INVALID
--------------------------------------------------
TECHNICIAN ATTESTATION
--------------------------------------------------
☐ Measured before intervention
☐ No values estimated
☐ Sequence followed
Name: __________________
Signature: _____________
Date: _________________
SYSTEM GOVERNANCE RULE
This system does NOT produce opinions.
Only results supported by:
- Measured baseline
- Authorized intervention
- Verified performance
are valid.
Without all three:
NO determination exists