Before a motor runs, a decision must be made.
That decision happens in the control circuit.
Switches are the simplest decision-making devices in HVAC systems.
Understanding switch logic prevents serious misinterpretation of voltage readings.
“Normally” describes the switch condition when it is:
Not energized
Not activated
It does not describe what the switch is doing during operation.
There are two basic types:
Normally Open (NO)
Normally Closed (NC)
Normal = resting state.
A normally open switch:
Does not allow current to pass in its resting state
Closes when activated
Example:
A thermostat calling for cooling.
When temperature rises above setpoint:
The thermostat closes the circuit.
From an evidence standpoint:
Voltage may be present on one side of a NO switch.
Current will not flow until it closes.
Voltage presence does not prove closure.
A normally closed switch:
Allows current to pass in its resting state
Opens when activated
Example:
A high-pressure safety switch.
Under normal conditions:
The switch remains closed.
If pressure rises too high:
The switch opens.
Current stops.
Voltage may appear across the open switch.
Understanding state prevents misinterpretation.
If a switch is closed:
Voltage drop across it should be minimal.
If a switch is open:
Full control voltage may appear across it.
Full voltage across a switch does not mean it is energized.
It means the path is broken.
Control chain:
Transformer → Thermostat → Float Switch → Pressure Switch → Relay Coil
If the pressure switch opens:
Current stops
Coil does not energize
Voltage appears across the open switch
Measurement must match logic.
When testing switches:
Identify whether it is NO or NC
Determine expected state under current condition
Measure voltage on both sides
Confirm continuity only when de-energized
Switch interpretation requires knowing design intent.
Seeing voltage on one side and assuming switch is closed
Seeing full voltage across a switch and assuming it is powered
Testing continuity on an energized circuit
Switch state must be evaluated safely and logically.
You stop if:
You do not know whether the switch is NO or NC
You test continuity on a live circuit
Voltage behavior does not match expected state
Switch logic must be understood before interpretation.
“Normal” describes resting condition.
Normally open switches close when activated.
Normally closed switches open when activated.
Full voltage across a switch usually indicates it is open.
Switch logic must be understood before testing.
What does “normally” refer to in switch terminology?
What happens to a normally open switch when activated?
Why might full voltage appear across an open switch?
Why must continuity be tested only when de-energized?
Why is knowing switch type critical before interpretation?
Previous Section:
Electrical Supply & Behavior (Section 2)
Next Lesson (3.2):
Relays and Contactors