Pyschrometric software

Psychrometric Air-Conditioning calculation (Android):  a PsychroAC 

calculate and plot air-conditioning cooling & dehumidification pyschrometric process; with precool air unit, heat pipe, run-around coil, heat recovery unit . . .

To take a glance at all pocketEngineer software and OS requirements, click Software List.

For digital psychrometric chart plotting, see Psychro Visual (Windows OS program)


Go to a PsychroAC module:

Main (AHU) module

aPsychroAC: Psychrometric Air-Conditioning processes  

Air-Conditioning psychrometric cooling & dehumidification process is a complex thing. Plotting psychrometric chart has never been an easy task for design engineers. Not anymore! with aPsychroAC, you can do various psychrometric calculations and plot psychro chart in a few clicks at anytime, anywhere...

Complex calculation software can be difficult to understand and use. aPsychroAC is intentionally designed not to be complex, but rather simple, practical, easy to understand and use. The main objective of engineering this software is to help HVAC designers in providing quick design solutions for the following air-conditioning design applications:

The OA inputs accept Conditioned Air (CA) conditions such as treated outdoor air from Precool Coil / Precool Air Unit (PAU), Heat Recovery Wheel (HRW), Run-Around Coil (RAC), Heat Pipe (HP), etc.

Precool Coil / PAU, HRW, RAC and HP calculations are included as separate modules with "Export CA" feature. The calculated SA (CA) conditions can be fed (exported) to the main AHU module as precooled (treated) outdoor air. You can recall back the PAU, HRW, RAC or HP module with its current activity's state retained. 


Highlights:


Design Approach explained . . . 

Two widely used design approaches to psychrometric air-conditioning calculations are modelled in aPsychroAC. They are

In the Carrier ESHF method, you start with specifying the coil performance, i.e., coil BF (bypass factor) that is generally representative of the type of equipment you intend to select. The supply air temperature condition is then calculated.

In the SA Temperature method, you start with fixing the supply air temperature condition. The coil performance is then calculated. The norm range of design temperature difference between SA and RA temperatures is about 15 - 22 oF (8 - 12 oC) with a common design target of 18 - 20 oF (10 - 11 oC).

The two methods give comparable results but not exactly the same (in aPsychroAC) for the following reasons:


Re-circulating or 100% OA System . . .  

Both re-circulating and 100% OA systems can be performed. For 100% OA system, it is more friendly to adopt the SA Temperature approach. Therefore, the option of 100% OA system is limited to the SA Temperature method. For 100% re-circulating system, input OA Airflow = 0.


Psychrometric Chart . . .  

No more manual plotting of psychro chart. With aPsychroAC, psychro chart showing the air-conditioning process is automatically plotted for each calculation. The psychro chart tells you the results in a graphical manner to visualize the process as shown in the chart below. The psychro chart can be saved as an image file for your calculation report.

OA=Outdoor Air; MA=Mixed Air; RA=Room Air; SA=Supply Air; off=off-coil; on=on-coil; ADP=coil ADP; GSHF=Grand Sensible Heat Factor; RSHF=Room Sensible Heat Factor

For digital psychrometric chart plotting, see Psychro Visual (Windows OS program)


Input Data. . .  

Only two information is required from your cooling load calculation, i.e., RSH (room sensible heat) and RLH (room latent heat).

OA ventilation airflow is usually determined by nos. of people x recommended outdoor air requirements.  

 

Effect of Coil BF (Bypass Factor) . . .  

Coil BF represents that portion of the air which is considered to pass through the coil completely unaltered.

Smaller BF has the following effects:

Cooling coil is not 100% efficient. Some of the air going through the coil is not cooled to the coil ADP temperature. In actual air-conditioning cooling coil application, the BF will be greater than zero. Carrier system design manual recommends the typical coil BF for various design applications as follows:


Relationship of Coil ADP, Supply Air & Chilled Water Temperature . . .  

Coil ADP (Apparatus Dew Point) or Effective Surface Temperature is the coil surface dew point temperature required to accomplish a cooling & dehumidifying process. Coil ADP is at the point where the GSHF line crosses the saturation line on the psychrometric chart. The relationship of coil ADP to SA & chilled water temperature is as follows:

 

Chilled Water Temp < Coil ADP < SA Temp 

In DX system, lower coil ADP means lower saturated suction (refrigerant) temperature at the compressor inlet. In chilled water system, lower coil ADP means lower chilled water supply temperature. This results in less efficient range (higher kW/Ton) of operation.

In aPsychroAC, you will be prompted when no coil ADP is found, i.e., the ESHF line or GSHF line does not intersect the saturation line as displayed below:

In the above situation, REHEAT is necessary to complete the process. 


Did you know? . . . slope of ESHF line  

From the ESHF value, one can calculate the slope of the ESHF line by using the following approximation:

slope of ESHF line, Tan (angle) = (1/2451)*[(1-ESHF)/ESHF]  


see downloadable intersection point example with CurveFit Tracer program (Windows OS)


Carrier ESHF Method - inputs 


 Carrier ESHF Method - inputs


Carrier ESHF Method - results


Carrier ESHF Method - results


Psychro chart plot


Calculation Method - Approach options


SA Temperature Method (with 100% OA option) 


Menu


Air Mixing module


Heat Pipe (HP) module


Precool Coil / Precool Air Unit (PAU) module


Heat Recovery Wheel (HRW) module


Run-Around Coil (RAC) module


Calculation Examples. . .  

For comparison example with Carrier E20, see example here . . . 

For Operating Room example with Heat Recovery device, see example here . . . 

For mixed air re-circulating system vs 100% outdoor air system, see downloadable example here...

 

The following design calculations are done with aPsychroACprogram.  

Worked Example 1 - recirculated system (in IP units)

Given:

Summer design conditions: 95 oF DB, 75 oF WB

Indoor design conditions: 75 oF DB, 50% RH  

RSH = 200 MBtu/hr

RLH = 50 MBtu/hr

OA ventilation airflow = 2000 CFM

BF = 0.15

Assume the total pressure of the suppy air fan is 3".

Worked Example 2 - recirculated + reheat (in SI units)

Given:

Outdoor design conditions: 34 oC DB, 40% RH

Indoor design conditions: 24 oC DB, 50% RH  

RSH = 60 kW

RLH = 40 kW

OA ventilation airflow = 4700 CMH

SA Temperature = 14 oC

Selected Coil BF shall be about 0.15

Assume the fan heat gain load is part of the Reheat load.

Worked Example 3 - 100% Outdoor Air (in SI units)

Given:

100% outdoor air summer air-conditioning system

Outdoor design conditions: 34 oC DB, 40% RH

Indoor design conditions: 24 oC DB, 50% RH  

RSH = 400 kW

RLH = 100 kW

SA Temperature = 14 oC

Assume the total pressure of the suppy air fan is 750Pa.

For digital psychrometric chart plotting, see Psychro Visual (Windows OS program)

aPsychroAC (Android)

Price:  at Android Market              

OS requirements: Android

Purchase & Download to your Android device: