Tunnel ventilation software

Tunnel Critival Air Velocity, aCriticalVelocity (Android)

calculates critical air velocities in tunnel fire ventilation for smoke control as per NFPA 502

To take a glance at all pocketEngineer software and OS requirements, click Software List.

a Critical Velocity : a quick design calculation for Critical Air Velocities in tunnels for smoke control   

To determine critical air velocities in tunnel ventilation for smoke control have never been easy. Not anymore! With aCriticalVel, you can do it in just a click away at anytime, anywhere...

Aim: creating a mobile design environment for the practising engineers & designers in today's mobile world.

Results: Instant solutions at your fingertips.

 

Highlights:

 

a Critical Velocity: design explained. . .  

aCriticalVel program employs the most commonly used model developed by Kennedy et al. to determine the ciritcal air velocity in tunnel ventilation for smoke control.

The critical velocity, Vc, is the minimum steady-state velocity of the ventilation air moving toward a fire that is necessary to prevent backlayering as illusrated in the diagram below.

To calculate the critical velocity, one needs to solve a coupled set of equations (as given below) by iteration. Therefore, it is best to let a computer program to perform this task

(Note: for symbol and detail, refer to NFPA 502)

 

acriticalVel is designed with a built-in calculators:

 

Design Fires in Road Tunnel . . . NFPA 502  

Typical fire heat release rates for tunnel vehicles are shown in the following table (after NFPA 502):


Did you know. . . SES program uses Kennedy model  

The Subway Environmental Simulation (SES) computer program for predicting ventilation flows in tunnel networks also includes a simple model to calculate critical velocity devised by Kennedy et al.  


Calculation Example 1: see to believe. . .  

The following design calculations are done with aCriticalVel program.  

Worked Example (in SI units)

Determine the critical velocity required to prevent backlayering of smoke in a cable tunnel. Assume a 5MW fire.

 

Critical Velocity Calculation

======================

Fire heat release reate, Qc (MW) = 5

Tunnel area, A (m2) = 14

Tunnel height, H (m) = 5.2

Tunnel gradient, grade (%) = 3

Approach air temp., Ta (oC) = 35

Approach air density, rho (kg/m3) = 1.134

Air specific heat, Cp (J/kg.oK) = 1039

 

Critical velocity, Vc (m/s) = 2.15

Airflow rate (m3/s) = 30.1

Hot-gas temp., Tf (oK) = 449.3

Hot-gas temp., Tf (oC) = 176.1 


Calculation Example 2: Road Tunnel . . .  

The following design calculations are done with aCriticalVel program.  

Worked Example (in IP units)

A road tunnel has the following parameters and data:

Tunnel area = 861 ft2, Tunnel height = 19.7 ft, Tunnel grade = 0 %, Fire heat = 102 MBtu/h, Air temp = 80.6 oF, Air density = 0.0687 lb/ft3, Air specific heat = 0.2484 Btu/lb.oF.

Calculate the critical velocity required to prevent backlayering of smoke.

 

Critical Velocity Calculation

======================

Fire heat release reate, Qc (MBtu/h) = 102

Tunnel area, A (ft2) = 861

Tunnel height, H (ft) = 19.7

Tunnel gradient, grade (%) = 0

Approach air temp., Ta (oF) = 80.6

Approach air density, rho (lb/ft3) = 0.0687

Air specific heat, Cp (Btu/lb.oR) = 0.2484

 

Critical velocity, Vc (ft/m) = 415.4

Airflow rate (ft3/m) = 357650

Hot-gas temp., Tf (oR) = 818.8

Hot-gas temp., Tf (oF) = 359.1

aCriticalVel - main page 


Air Density & Air Specific Heat calculator


customised area calculator


customised area calculator


aCriticalVel (Android)

Price:  at Android Market              

OS requirements: Android

Purchase & Download to your Android device: