Psychrometric software
Psychrometric software
To take a glance at all pocketEngineer software and OS requirements, click Software List.
Go to a PsychroAC module
:
The following design calculations are done with aPsychroAC program.
Your designer has completed the heat load calculations for a Gallery space using Carrier E20 (HAP) program. A copy of the E20 printouts is given to you for checking. Your role is to check the results with the handy tool of aPsychroAC program.
The design information you have extracted from the E20 printouts are as follows:
a) RSH = 254666 W
b) RLH = 81624 W
c) OA ventilation airflow = 3656 l/s
d) OA conditions: 32.2 oC DB / 26.0 oC WB
e) Room design conditions: 24 oC / 53% RH
f) Coil BF = 0.05
g) Supply Air Temp = 13 oC
h) Fan static = 750 Pa
i) Draw-thru fan configuration
-----------------------------------------------------------------
You compared the E20 printouts with aPsychroAC results (using Carrier ESHF method) as follows:
Tdb = Dry bulb temp (oC)
RH = Relative humidity (%)
w = Moisture content (g/kg)
m = Mass flowrate (kg/s)
h = Enthalpy (kJ/kg)
OA = Outdoor Air
RA = Room/Return Air
MA/on = Mixed Air / on coil
off = off coil
Comments::
For illustration purposes, aPsychroAC program is used as a quick design check tool.
Worked Example 4 - psychro chart plot
Worked Example 4 - Carrier E20 psychro chart plot