Module 5.09 - Calculation of Design Coefficient
Inside Film Coefficient, hi = 948.9 Btu/(hr·ft2/·°F)
Outside Film Coefficient, ho = 1217.7 Btu/(hr·ft2·°F)
Inside Diameter, di = 1.33 in
Outside Diameter, do = 1.5 in
Heat Load, Q = 399200 Btu/hr
Log Mean Temperature Difference, LMTD = 28.85 °F
Inside Film Coefficient based on Outside Diameter, hio= 841.4 Btu/(hr·ft2·°F)
Clean coefficient, UC = 497.6 Btu/(hr·ft2·°F)
Inside Fouling Resistance based on Outside Diameter, Rdio = 0.001 hr.ft2°F/Btu
Total Fouling Resistance, Rd = 0.002 hr.ft2°F/Btu
Overall Design Coefficient, UD = 241.7 Btu/(hr·ft2·°F)
Heat Transfer Area, A = 57.3 ft2
Pipe Length, LP = 145.8 ft