Example 5.9: A hot fluid enters a concentric pipe at a temperature of 300 °F and is cooled by a fluid that enters the heat exchanger at 70 °F and leaves at 190 °F. Calculate the mean temperature difference for the following cases:
(1) Counter-current flow, (2) co-current (parallel) flow, (3) 1-2 Multipass, (4) 2-4 Multipass,
(5) 1-1 Cross-flow, (6) 1-2 Cross Flow heat exchangers.
Solution:
Inlet temperature of hot fluid, T1 = 300 °F,
Outlet temperature of hot fluid, T2 = 200 °F,
Inlet temperature of cold fluid, t1 = 70 °F,
Outlet temperature of cold fluid, t2 = 190 °F.
(1) Countercurrent Flow:
ΔT at the hot end, Δth = T1 - t2 = 110 °F,
ΔT at the cold end, Δtc = T2 - t1 = 130 °F
(2) Co-current Flow:
ΔT at the hot end, Δth = T1 - t1 = 230 °F
ΔT at the cold end, Δtc = T2 - t2 = 10 °F
For other arrangements, a temperature correction factor, FT, is needed that is based upon two additional parameters R, and S.
Temperature correction factor, FT, (Figure 5.1)
(3) 1-2 Multipass: FT = 0.86, ΔT = (0.86)(119.7) = 102.9 °F
(4) 2-4 Multipass: FT = 0.98, ΔT = (0.98)(119.7) = 117.3 °F
(5) 1-1 Cross-flow: FT = 0.9, ΔT = (0.9)(119.7) = 107.7 °F
(6) 1-2 Cross-flow: FT = 0.98, ΔT = (0.98)(119.7) = 117.3 °F