Example 3.15: Moist air at 70 °F dry-bulb and 45 °F wet-bulb temperatures is to be processed to a final dew point temperature of 55 °F by adiabatic injection of saturated steam at 230 °F. The feed rate of dry air is 200 lb/min. Find the final dry-bulb temperature of the moist air and the steam required in lb/h.
Solution
Find enthalpy of the steam hg = 1157 Btu
Δh/ΔW = hg = 1157 Btu
Use the protractor to join the origin with Δh/ΔW = 1157 Btu and generate a reference line.
Locate State 1 (t = 70 °F, t* = 45 °F) ® W1 = 0.00070 lbw/lba
Draw a line parallel to the reference line passing through State 1 and generate a condition line.
Draw a horizontal line from final dew point td = 55 °F.
Locate intersection of these two lines that defines state 2.
Read properties of state 2. W2 = 0.00920 lbw/lba
mw = ma(W2 - W1) = 200´60´(0.00920 - 0.00070) = 102 lb/h