Pipe sizing software
easy Pipe Friction - Loop pipe pressure drop (head loss) calculation (Windows)
multi-purpose solutions for total pump head, pipe network pressure drop calculation in series (branch) pipes + loop ring main pipe network
To take a glance at all pocketEngineer software and OS requirements, click Software List.
Water Pumping Mainline Pressure Drop
- working example with ePF Loop program (Windows)
Application example: Water Pumping Mainline
System design: To pump water from Point A to Point B
Pump flow rate: 240 l/s total
Nominal discharge pressure required at discharge outlet: 0.2 bars
Elevation difference = 20 m
Pipe material: Ductile iron
600mm diameter mainline pipe:
total length = 600m
6 nos 90o standard elbow
9 nos 45o standard elbow
2 nos Tee
1 no magnetic flow meter
400mm diameter pump suction/discharge line pipe:
total length = 10m
2 gate valve
1 check valve
2 reducer/expander
1 no 90o elbow
Applied Working: Refer to the system schematic sketch below, calculate the total pump head required for the system.
In ePF Loop program, the total pressure drop for the system is adding all components causing resistance to flow. You're in control the whole calculation experience.
input and result screen snapshots . . .
total pressure drop (head loss) calculation main page
series pipe pressure drop calculation page
Results Deliverable:
In ePF Loop program, the results are saved in text file. You can then reformat, cut & paste, and so on to suit your desired format.
>> Application example (2-Loop ): Two-loop pipe network flow and pressure drop analysis
>> worked example (2-Loop): Two-loop Hydrant ring main pipe pressure drop analysis
>> worked example (Series + Loop): Hydrant ring main system
>> worked example (Series): Wet Riser system
>> see results comparison example: ePF Loop vs a 3rd party program
>> Analysis example: see Loop pipe ring main.
>> Steam pipe pressure drop example: see Pressure loss in steam pipe.