Lab 4 - Non-Ideal Transformers
Purpose
To determine the transformer properties via open-circuit, short-circuit, and load tests on a non-ideal iron core transformer. The voltage regulation and efficiency for various load conditions will be calculated and compared with the results of the load test.
Introduction
Since iron has non-linear magnetic characteristics, the iron core transformer is essentially a non-linear device, with internal losses and leakage. We will model the operation of the device with an appropriate linear equivalent circuit which accounts for both losses and leakage. Using this equivalent circuit, we then can predict transformer behavior with sufficient accuracy. Moreover, this equivalent circuit has parameters which may be determined by simple tests that we will perform.
Equivalent Circuit 3a (Open-Circuit)
Part 1: Equivalent Circuit Model (see test circuits for comparison)
At lower frequencies, the physical transformer can be represented by an equivalent circuit as shown in Figure 3c. If the voltage in the primary and the leakage reactance are neglected the approximate equivalent circuit 3d can be used to predict the performance of the transformer.
Open Circuit Model using 3a and 3d & 3b and 3d:
Equivalent Circuit 3b (Short-Circuit)
Equivalent Circuit 3c
Equivalent Circuit 3d
The results of the equivalent circuits will allow for the regulation and efficiency calculations required in the results section. Keep in mind the equivalent circuit is from the primary side. The test load (RL and XL ) must be multiplied by (N1/N2)2 so that all the parameters are referred to the high-voltage (primary) side. Alternatively, some parameters may be transformed to the low-voltage side.
Be careful not to mix voltage and current from one side with the impedance value from the other side.
Part 2: Efficiency
η = output power/input power, where: input power = (outut power - losses)
Wo = Vo ∙ Io ∙ cos(θo)
The iron losses are obtained from the open-circuit test
the copper losses are obtained from the short-circuit test
Part 3: Regulation
The voltage regulation of a transformer, at a certain load, is defined as the percentage rise in the secondary voltage when the load is removed.
∈ = (Vno load - Vfull load )/Vfull load
Test Circuits
Circuit 3.1: Open-Circuit Test
Procedure
Testing:
Record the model number, voltage, current, and power ratings of the transformer.
Do not exceed these values.
Open-circuit Test:
Use AC for both voltage and Current. Use mA mode for the current measurement.
Circuit 3.2: Short-Circuit Test
Warning: Turn the autotransformer down and off before
carrying out the short circuit test.
Short-circuit Test:
For the short-circuit test apply the test voltage slowly
until the rated current is achieved in the secondary.
A small input will produce a large current in the secondary.
Less than 10 volts is enough to circulate the rated secondary current.
Load Test:
Circuit 3.3: Load Test
Results
Open Circuit Test
Short-Circuit Test
Load Test
For each test, discuss your results. Include reference to the introductory theory, and where departures from the ideal transformers occur.
Questions