Install closet lighting.
Garage light switch - move it into the garage
Spa: The cable to the hot tub is not protected by conduit and susceptible to accidental damage; a potential hazard.
--
INSPECTION
(1) Main panel [11.1-3]: Ten 120 volt breakers and four 240 volt breakers. There is no main breaker present to provide overcurrent protection of the supply cable or easy shutoff of all circuits. Defects noted include: (A) Screws missing; (B) cables not secured with clamps; (C) vague labeling; (D) Four of the 120 volt circuits are double tapped.
(2) Distribution defects [11.4]: (A) The cable to the garbage disposal in the undersink cabinet is not protected by conduit and there is no grommet or strain relief device installed. (B) A cable terminates outside a junction box; (C) Overhead supply to the shop is low and susceptible to accidental contact or damage. (D) The cable to the hot tub is not protected by conduit and susceptible to accidental damage; a potential hazard. [Addressed in Positive Electric bid]
(3) Outlets [11.5]: (A) loose outlet was discovered in the north wall of the NE bedroom. (B) Some outlets are worn and will not securely hold a two prong plug. (C) Hot and neutral connections are reversed at outlets on the west side of the kitchen.
(4) Ground Fault Circuit Interrupters (GFCIs) [11.6]: No ground fault interrupters were identified in this house. [Addressed in Positive Electric bid]
(5) Smoke detector: Only one. It is generally recommended smoke detectors are installed in every bedroom.
ELECTRICIAN LIST
(1) Main panel
Inspection comments: There are ten 120 volt breakers and four 240 volt breakers. There is no main breaker present to provide overcurrent protection of the supply cable or easy shutoff of all circuits. Four of the 120 volt circuits are double tapped.
Install main breaker
Remove the 4 double taps (install 2 120 breakers to remove double tap)
Secure cables with clamps (install RX clamps in panel (1-1/4", 1-1")
Install no lox on all wires in panel
Replace missing screws
Correctly label the breakers
(2) Distribution defects
Shed: Overhead supply to the shop is low and susceptible to accidental contact or damage.
Hot tub: The cable to the hot tub is not protected by conduit and susceptible to accidental damage.
A cable terminates outside a junction box (install j-box in attic for open wire)
(3) House in general
Update worn outlets
(4) Master bathroom
Install GFCI on each side of sink
Install ceiling light and fan
(5) Hall bathroom
Install GFCI outlet
Install ceiling light
(6) Master bedroom
Install smoke detector
Install outlets on either side of the bed
(7) Office
Install outlet in closet, for iron
Install closet light controlled by door switch
(8) Garage
Install GFCI outlets
(9) Shed
Install GFCI outlets?
Fix open junction box
Install outlet nearer to camper
Install outlet on ceiling behind camper (for another light source)