Bermad MC406
Default Configuration Settings
Default MC406 Settings tested in-office by SigSense are as followings:
Parity: 8N1
Connection: RS485
Baud: 9600
Slave Addr: 1
Register: 1687/1688
Function: Holding
Data Type: Float32
Byte Order: CDAB
Meter Telemetry Registration
The below options are the critical details for the Meter Telemetry Registration on the DQP Portal
Modbus (Recommended)
LID Device: Captis Multi v2
Telemetry Flow Units: kL
Scaling Factor: 1
Pulse
See the manual linked at the bottom of the page for adjusting your meter to match the units to those on your registration.
If you have any persistent issues contact Sigsense or Bermad Support
Installation Overview
This page will cover the process that can be followed to integrate a Captis Multi with a Bermad MC406 via Modbus.
A detailed step-by-step can be found in subsequent sections of this guide. A more concise outline of the installation is as follows:
Connect Captis wiring to MC406 headers
Enable MC406 Modbus communications, verify DAS communication
Adjust the MC406 Modbus activation window to match Captis
Verify DAS communication prior to finalising install on DQP Portal
- MC406 Wiring
1.1 Pulse Wiring
1.1 (a) Pass Captis Wires Through Gland
Strip back and pass the following cores through the MC406 cable gland:
White
Black
Blue
Red
1.1 (b) Terminate Wires To the Two Positive or Negative Terminations
Ensure you connect the white and black wires to the same loop - generally 1 & 2 for positive and 3 & 4 for negative. Positive indicates forward flow and negative indicated a reverse direction of flow.
1.2 Modbus Wiring
1.2 (a) Pass Captis Wires Through Gland
Strip back and pass the following cores through the MC406 cable gland
Black
Yellow
Orange
Blue
White
1.2 (b) Terminate Connections
Remove the connector (circled red) and terminate the Captis connection as below
MC406 GND > Captis Black
MC406 B > Captis Yellow
MC406 A > Captis Orange
Inside the MC406, securely terminate the Captis cable cut detection. Ensure sufficient insulation to prevent risk of short circuits. Solder and heat shrink or boot-lace ferrules are recommended.
Captis Blue > Captis White
1.2 (c) Close MC406
Connect terminated MC406 modbus connector to PCB, ensure cable cut leads are securely connected and insulated, reinstall required MC406 components (e.g battery) and close converter.
2. Test DAS Communication
Due to the extensive battery saving features of the MC406, it is necessary to follow the below process to ensure converter battery life and reliable RTU communication.
2.1 Enable MC406 Modbus Output
For assistance navigating the on screen converter menu, please refer to the MC406 manual attached at the bottom of this page.
Using the navigation buttons, access the device function settings and change F46 to a value of 12
2.2 Wake Captis
Using the included magnet, wake up the Captis by touching it to the 'Wake' engraving.
Wait for the Captis light to come on, and then turn off (approx. 2 minutes)
2.3 Verify DAS Flow
Using a Laptop, Tablet, or Phone log in to the WaterNSW DAS via https://app.eagle.io/login
On the left side bar, identify the correct site and click on it.
Press 'Dash' in the top right
Inspect Dashboard for flow total and compare to MC406 display
If you're having issues accessing or using the DAS, feel free to give SigSense a call (07 3053 5229) and we'll help you verify the DAS reading.
Once the DAS reading has been confirmed, DO NOT WAKE THE CAPTIS AGAIN, CHANGE THE WIRING OR INTERFERE WITH THE CABLE CUT.
3. Adjust MC406 Modbus Activation (Battery Powered Only)
In step 2 we permanently enabled the modbus output of the meter to allow for the LID, meter and DAS to be tested 'end-to-end'. To permit greater battery life where no external power (e.g DC / Solar) is available, we must now change the Modbus activation window of the MC406 to match and sync with the installed Captis.
Once changed, the MC406 will keep the modbus interface active until it receives a Modbus request. The MC406 will then disable the modbus output and begin enabling it on the interval defined by the setting, F46. As a result, it is important the next measurement request be the hourly scheduled measurement from the LID. Do not wake the device, interfere with the cable cut or disconnect the cable once beginning this section as it will result in the Captis measurement and MC406 activation intervals being out of sync.
Currently, all Captis devices used in NSW Non-urban metering have 60 minute logging intervals (on the top of each hour). This requires a setting of F46 = 11.
For assistance navigating the on screen converter menu or converter setting details, please refer to the MC406 manual attached at the bottom of this page.
3.1 Adjust MC406 Modbus Interval
For assistance navigating the on screen converts menu, please refer to the MC406 manual attached at the bottom of this page.
Using the navigation buttons, access the device function settings and change F46 to a value of 11.
Do not wake the device, interfere with the cable cut or disconnect the cable after completing this section.
4. Post installation DAS Verification
Although communication was verified in step 2, SigSense recommend a further check of the DAS at least 1 day after installation to ensure the MC406 activation window has been correctly set and measurements are successful.
4.1 Final DAS Verification
Using a Laptop, Tablet, or Phone log in to the WaterNSW DAS via https://app.eagle.io/login
On the left side bar, identify the correct site and click on it.
Press 'Dash' in the top right
Inspect Dashboard for flow total and ensure hourly measurements are successful
If you're having issues accessing or using the DAS, feel free to call (07 3053 5229) and we'll help you verify the DAS reading.
Product Manual
View the product manual and further wiring information below or click on the top right to download the manual.