ABB AquaMaster 3
Contained on this page is the default configuration and wiring information for an ABB AquaMaster 3 Transmitter. The information contained in this guide was determined with support from ABB and verified by testing on an AquaMaster 3 Transmitter.
Default Configuration Settings
Baud rate: 19200
Data Parity & Bits: 8/E/1
Slave Address: 1
Data type: Int32
Endianness: ABCD
Register function: Holding
Totalised Forward Flow Address: 12003
Wiring to Captis
A wiring diagram for the AM3 Transmitter using the AM3 WABC2010/03 cable can be seen below. Please note that as the AM3 transmitter does not provide +5V for the serial communication it will be necessary to include pull-up and pull-down resistors as outlined in the below wiring diagram.
Product Manual
View the product manual below or click on the top right to download the manual.