Quick answer: To calculate airflow for a room, multiply the room volume (m³) by the target air changes per hour. The answer gives airflow in m³/h. Multiply by 0.5886 to convert to CFM. For heat removal, divide the heat load in kW by 1.2 times the allowed temperature rise in °C to get airflow in m³/s.
Planning aid notice: these methods give early estimates. They do not replace a site survey or an engineering design.
Volume (m³) = Length (m) × Width (m) × Height (m)
For a sloped roof, use the average height. For L shaped rooms, split the room into rectangles and add the volumes.
Airflow (m³/h) = Volume (m³) × ACH
ACH = Airflow (m³/h) ÷ Volume (m³)
ACH tells you how many times per hour the full volume of room air gets replaced with outdoor air.
Worked example: a workshop measures 20 m × 12 m × 6 m.
Volume = 20 × 12 × 6 = 1,440 m³.
Assumed target = 8 ACH.
Airflow = 1,440 × 8 = 11,520 m³/h.
In CFM = 11,520 × 0.5886 ≈ 6,780 CFM.
Not all airflow counts toward ACH. Keep these three apart.
Outdoor air ventilation. It brings outdoor air in. It counts toward fresh air ACH.
Exhaust flow. It pushes indoor air out, so outdoor air enters. It counts, if replacement air enters from outside.
Recirculation. It moves indoor air around inside. It does not count toward fresh air ACH.
An air circulator moving 10,000 m³/h inside a room does not give the room any fresh air changes. It only mixes the existing air.
Airflow (m³/s) = Heat load (kW) ÷ (1.2 × ΔT)
ΔT is the temperature rise you accept between incoming outdoor air and outgoing indoor air, in °C.
Worked example: a compressor room gains 15 kW of heat. You accept a 4°C rise.
Airflow = 15 ÷ (1.2 × 4) = 15 ÷ 4.8 = 3.125 m³/s.
In m³/h = 3.125 × 3,600 = 11,250 m³/h.
In CFM ≈ 6,620 CFM.
Limits: this formula covers sensible heat only. It ignores moisture and assumes outdoor air is cooler than indoor air.
Velocity (m/s) = Airflow (m³/s) ÷ Area (m²)
Worked example: 3 m³/s passes through a 2 m² louvre. Velocity = 1.5 m/s.
Use this to check inlet sizes. Very high inlet speeds raise noise and resistance.
Energy (kWh) = Power (kW) × Operating hours
Cost = Energy (kWh) × Tariff per kWh
CFM to m³/h. 1.699
m³/h to CFM. 0.5886
m³/min to CFM. 35.31
m³/s to m³/h. 3,600
m/s to ft/min. 196.85
mm WG to Pa. 9.807
Counting circulator airflow as ventilation. Only exhaust or supply with outdoor air counts.
Using free air ratings for ducted fans. Ducts and louvres cut airflow. Use airflow at the expected static pressure.
Ignoring inlet area. Exhaust fans cannot move air the building cannot replace.
Mixing units. Convert everything to one unit system first.
Treating the estimate as a design. Ask an engineer to confirm the plan for large or hazardous sites.
How do I calculate CFM for a room?
Multiply the room volume in cubic feet by the target ACH, then divide by 60. Or calculate in m³/h and multiply by 0.5886.
What is a good ACH for a factory?
It depends on heat load, occupancy, processes and local rules. Ask a ventilation engineer to set the target.
Can I use the ACH method for comfort cooling?
No. Comfort cooling depends on air speed at the worker. ACH measures air exchange.
Why does my exhaust fan move less air than rated?
Resistance from louvres, ducts, guards or blocked inlets reduces airflow. So do low voltage and dirty blades.
What does ΔT mean?
ΔT means the temperature difference between incoming and outgoing air.
Is there a spreadsheet for these formulas?
We are preparing a free downloadable toolkit. Check the Resources page for updates.
For published airflow figures of specific models, see the official Action Aire catalogues.
Ready to choose a fan for your airflow target? Use the Fan Selection Framework.