1. Line Quality and Representation Errors
Walls, roof lines, windows, and doors are not drawn using thin lines.
Electrical symbols are not drawn using thick lines.
Labels have no light guidelines or inconsistent lettering height (not 3mm).
2. Circuit and Wiring Errors
Circuit lines for lighting intersect with other circuit lines.
Circuit home runs are missing or not pointing back to the panel board.
Convenience outlet circuit lines are not drawn beside the wall.
Parallel lines in the convenience outlet symbol do not touch the wall.
Wires cross over fixtures in an illogical or unsafe manner.
3. Lighting Circuit Errors
More than 20 pin lights are assigned to a single 15-ampere circuit.
Switches are not assigned properly to pin lights.
Chandelier does not have an assigned switch.
Pin light does not have an assigned switch.
4. Convenience Outlet Circuit Errors
More than 15 outlets are assigned to a 20-ampere circuit.
Convenience outlets are placed too far from intended appliance locations.
Incorrect placement of outlets in wet areas (e.g., near sinks without proper protection).
5. Dedicated Circuit Errors
Refrigerators, ranges, electric motors, chandeliers, air conditioning units, or washing machines lack dedicated circuits.
6. Safety and Compliance Issues
Panel board placement does not follow accessibility and safety standards.
Overloaded circuits (too many outlets or fixtures assigned to a single circuit).