Air handling unit (AHU) is used primarily for air conditioning purposes, which includes heating, cooling, humidity control and cleaning. This AHU is a primary air return type, for variable air volume system (VAV). It has three energy efficient features: an Energy Recovery Wheel (ERC), a Water Source Heat Hump (WSHP) and Tricoil Unit. For air cleaning or filtration, MERV13 air filters are used to remove dust, pollen, allergens, and microbes from the air stream. UV lighting is used in the AHU to reduce the possibility of microbial growth on the coils and in condensate pans. [1]
At the beginning of the AHU, there is an Energy recovery wheel (ERC). It is a desiccant wheel which runs between the outside air and the normal return air. The return air is separate from the mixed exhaust air, which comprises air returned from the first and second floor restrooms. Through heat and moisture exchange in the motorized wheel cycle, the air handling unit can decrease a lot of heating and cooling load. For example, in the winter, outside air is preheated by exhaust air. The load design temperature before the wheel is 3 degree Fahrenheit, and after the wheel it is 64.4 degree Fahrenheit. For this reason, it is called energy recovery.
A Water Source Heat Pump (WSHP) is for heating or cooling outside and return mixed air, using geothermal water as its source. During the summer, the WSHP works as chiller, where the cool water from geothermal system acts as a source of cooling for the condenser. During the winter, it works as a heat pump, where the hot geothermal water acts as heating source for the evaporator. In both conditions, the refrigerant (Glycol) completes heat transfer in the primary coils of the AHU.
After passing through the ERC, the mixed air enters the Tricoil Unit, which is composed of three coils. The first, second and third coils are called the pre-cooling coil, primary coil and the downstream third coil. To understand how the system works, consider an instance in the summer. In this situation, some of the sensible heat in the mixed air is picked up in the first coil, which reduces the cooling load. The mixed air then goes through the second coil, where it undergoes refrigeration and dehumidification processes, becoming cold and dry supply air. Finally, in the downstream third coil, the cold, dry supply air is warmed up a bit for comfort, but stays nice and dry. The coolness picked up by the reheat coil in this process is then transferred back to the pre-cooling coil to restart the sequence.
This psychometric chart shows primary return air conditioning process in the summer, for a constant air volume system. W is outside air (OA) point (after passing through ERC), N is inside air point which is same as return air (RA), and mixes with outdoor air (OA), approaching point C. It is cooled and dehumidified by primary cooling coil in AHU, reaching point L where is becomes cold and dry air. But for occupants' comfort, it is then reheated, becoming supply air (SA) at point K. After that, it was blown by fan at the end of AHU, and was distributed in working area. After exchanging heat and humidity with people and environment, it becomes return air (RA) which comes back to point N, and restart the sequence.
This psychrometric chart also shows primary return air conditioning process in summer, but it is a bit different as it has heat recovery addition. W is outside air (OA) point (after passing through REC), N is inside air point which is same as return air (RA), and mixes with outdoor air (OA), approaching point C. It is cooled but not dehumified by pre-cool coil, becoming new point C, then It is cooled and dehumidified by primary cooling coil, reaching point L which is machine dew point. It is then reheated, becoming supply air (SA) at point O. After that, it was blown by fan and was distributed, becoming return air (RA) which comes back to point N, and restart the sequence.
- Manufacturer: Berner International Corp.
- Model: Unit No : AHU-1
- Total cfm: 12,400
- Min Outdoor Air cfm: 2,720
- Make, Model: Berner Energy Recovery, 9812