Arc Fault Protection

690.11 Arc-Fault Circuit Protection (Direct Current). 

Photovoltaic systems operating at 80 volts dc or greater between any two conductors shall be protected by a listed PV arc-fault circuit interrupter or other system components listed to provide equivalent protection. The system shall detect and interrupt arcing faults resulting from a failure in the intended continuity of a conductor, connection, module, or other system component in the PV system dc circuits. 

Informational Note: Annex A includes the reference for the Photovoltaic DC Arc-Fault Circuit Protection product standard. 

Exception: For PV systems not installed on or in buildings, PV output circuits and dc-to-dc converter output circuits that are installed in metallic raceways or metal-clad cables, or installed in enclosed metallic cable trays, or are underground are permitted without arc-fault circuit protection. Detached structures whose sole purpose is to house PV system equipment shall not be considered buildings according to this exception. 