In accordance with 21 (1) (a-c) of the Otago Regional Plan for Water:
This effluent plan was prepared in December 2024 and will be reviewed by December 2025 with the results noted in this section with changes recorded automatically. The contents of this Effluent Management Plan are available to the regional council on written request.
In accordance with 21 (2) (a-e) of the Otago Regional Plan for Water
The physical location of the farm where the effluent system is located is 376 Brookstead Rd, Georgetown and the effluent is applied to the same address. Refer to the legal descriptions below for full details.
Brookstead Ltd
484 Brookstead Road
Oamaru 9491
Rhys Hamilton
Ph 0274 317 077
LOT 1 DP 27297 LOT 1 DP 10257 SECS 53-54 PT SEC 52 BLK VI AWAMOKO SD
Existing Consents
RM24.754.01 To discharge animal effluent to land and to use an animal effluent system for the purpose of operating an animal effluent system, expires 2035.
RM23.245.02 To discharge contaminants to land for the purpose of undertaking intensive winter grazing, expires 2028.
In accordance with Schedule 21 (2) (e) of the Otago Regional Plan for Water.
Effluent Discharge Area: 160ha (152ha pivot and 8ha fixed grid).
The system consists of a sand trap draining to a sump with solids separator which discharges into a plastic lined storage pond. The pond is 2,180 cubic metres. The system discharges primarily by injection through the irrigation system into three of the four pivots, parts of the fixed grid to improve fertility in targeted areas, and in shoulder seasons through pods for an hour at a time.
No effluent is to be discharged within:
20m of the farm boundary or further if necessary to prevent spray drift crossing the farm boundary
50m of any surface watercourse.
50m of any subsurface drainange.
100m of any water abstraction point should any be established.
200m of place of dwelling or assembly not on the property.
Cows: Up to 990 cows milking twice a day peak milk.
In accordance with Schedule 21 (2) (e) (iv) of the Otago Regional Plan for Water
Click here to access the S - Map for Brookstead. Awamoko soils are found on the flats but the effluent application area consists of both Ngapara soils which are low risk FDE Category D land less than 7 degrees slope and high risk Category C when over 7 degrees slope, and Brookstead soils which are high risk FDE Category C over 7 degrees of slope. According to Dairy NZ industry best practice the maximum effluent irrigation depth allowed is 10mm when a soil water deficit is identified that is greater than the application rate. This is achieved by application using low rate irrigation, specifically centre pivots which apply as little as 1.5mm and up to 6mm, and also through effluent pods which apply at a rate of 8mm per hour and are controlled by timers to achieve the correct rate of application between shifts. Bucket tests are used to verify actual application rates and soil moisture deficit is determined a minimum of 24 hours after rain by the Aquacheck data and graph in the effluent area which gives irrigation recommendations for staff to consider. The application rate must not result in exceeding Field Capacity.
Deep silt loam.
Well drained.
High profile available water (166mm).
FDE risk category C (over 7 degrees) and D (under 7 degrees).
Moderately deep silt.
Well drained.
Moderate to low profile available water (69mm).
FDE risk category C.
Known subsurface drains are located on the CSA map below and are not within the effluent application area.
Effluent Critical Source Areas are avoided with the exception of the upper reaches of some dry swales under pivots or fixed grid low rate effluent application which only flow during saturation conditions from rain. This risk is managed because effluent isn't applied unless there is a soil moisture deficit and the swale under the pivot near the cattle yards has no effluent applied to it due to the short run directly to a waterway. In general effluent is targeted to bony areas to build up soil structure and fertility rather than to swale floors where nutrients naturally concentrate anyway.
See Waterway and CSA Management Plan in Farm Environment Plan.
In accordance with Schedule 21 (2) (f) of the Otago Regional Plan for Water
The effluent pump is maintained monthly as part of the dairy shed inspection. For major issues that can't be repaired in-house contact as relevant the electrician Waitaki Electrical on 0800 277 244, or Ahoy Engineering on 0210 300 944. Waterforce Oamaru can supply parts for self repair.
All maintenance and repairs are recorded in the hard copy Irrigation Maintenance record.
Soil Moisture Deficit
Check that Aquacheck data and graph shows adequate soil moisture deficit.
Running Straight Effluent:
Check Outlet is Open
Pivot: tap open and control valve to 'open.'
Pods or Fixed Grid: relevant tap open.
Injecting into irrigation:
Open outlet into irrigation pond.
Open irrigation tap outlet - water will flow back up the line.
Start pump
Ensure VSD is set at correct setting for application (see below).
Prime pump with all taps closed (20-30 pumps).
Start pump and stirrer.
Slowly open self cleaning screen (green tap).
Slowly open blue main tap keeping pressure over 35psi.
Slowly shut outlet into irrigation pond.
Post Start Checks
Ensure effluent is being dispersed as intended.
Ensure pivot valve is on auto.
Check for leaks or malfunction in the system.
Monitor system consciously while running to ensure there is no run off.
Take care not to kink the pod feeder hose - ensure a 3m diameter loop when pulling back. Shift pod approximately 40m each time and prioritise safe placement for both yourself and the environment when considering terrain.
Shut Down
Turn pump and stirrer off.
Shut blue main tap at pump.
Shut all outlet taps (if running straight effluent or not intending to restart).
Recording
Record application in the hard copy Irrigation Scheduling Sheet.
All paddocks have slopes which can cause potential run-off. Timers and bucket testing to be used to adjust application depth according to soil moisture.
Pivot tracks can cause run off. Position pods away from pivot ruts so the effluent falls at least 5m short.
Water troughs to be avoided by pod.
Effluent is not to be applied to gully floors.
Note: original controlled copies of all farm Operational Procedures are located here.
Solids are spread periodically as limited by storage, and cannot be spread on the same area more than once every two months, preferably by incorporating into cultivation of land.
Solids are not spread onto land when the soil moisture exceeds field capacity; or within 20 metres of waterways, or the farm boundary.
Solids are also not spread where previous applications are still visible on the ground, or where soil moisture exceeds field capacity.
Hazardous substances, hazardous waste and human effluent is not to be added to the effluent system.
In accordance with Schedule 21 (2) (g) of the Otago Regional Plan for Water
Inspect the system for leaks, ponding and run off each time the pump is started up and in between shifts as well as in passing throughout the day. Weak points are at the manifolds, the hydrants and the feeder hose. Check for kinks in the hose, holes, leaks or blowouts. Check that the sprinklers are under pressure and turning normally. Ensure the sprinkler is not located in a swale or siphoning. Leaks, ponding, run off and flow through drainage can cause the effluent to enter a waterway which must not occur.
As part of the monthly shed inspection check the area below the storage pond for wet patches, areas of grass that are greener than the grass surrounding it or any other signs of leaking from the pond. Include a check of the stone traps to ensure they aren't becoming blocked.
Bucket tests are completed annually on the irrigators to verify application depth and rate.
Inspections, audits and certificates from North Otago Irrigation Company, Fonterra (QCONZ), and Otago Regional Council are kept on record.
In addition to the checks after start up staff are to check the same components while the effluent is running if they are passing the irrigator at least once a day.
All staff are to report any odour from the system if it reaches the farm boundary, or if any complaints are received about the effluent system including odour.
Aquacheck data and graph verifies that over application of effluent has not occurred.
When a leak, ponding or run off are discovered the pump must be turned off immediately and the fault reported to the farm owner within half an hour. Where possible the problem should be fixed immediately and recorded.
Effluent applications are recorded in the dairy diary and reported at audits for NOIC, ORC and Fonterra.
In accordance with Schedule 21 (2) (h) of the Otago Regional Plan for Water
Date of last test: 22nd June 2022
Date next test is due: 22nd June 2027
Pond Drop Test Report and Graph are available.
The effluent storage facility also has a Dairy Effluent Storage Calculator and will be checked by a suitably qualified person to ensure permitted activity status.
In accordance with Schedule 21 (2) (i) of the Otago Regional Plan for Water
The effluent system has several measures to prevent discharges to water:
Staff training (template)
Monitoring
Low pressure/high flow automatic pump cut out with Variable Speed Drive.
Low rate application systems.
Cooler water is metered and recycled to reduce volume of effluent produced.
Automated text message timer prevents accidental over watering. It's important not to become complacent and rely on the automation.
Large storage pond. We never know when we will need to pump to storage or when we can empty the storage so we use every opportunity to drain effluent out of storage and apply to the paddocks. If there is effluent in storage and the soil has the appropriate soil water deficit to irrigate then emptying storage is a priority.
Stirrer is proactively used to prevent buildup of solids. Solids are removed manually if needed.
Low water use creates less effluent with recirculated cooler water for the wash down hoses.
Storm water diversion from the cow shed roof prevents fresh water from unnecessarily occupying capacity in the effluent system during heavy rain.
In accordance with Schedule 21 (2) (j) of the Otago Regional Plan for Water
When a leak, ponding or run off are discovered the pump must be turned off immediately and the fault reported to the farm owner within half an hour. Where possible the problem should be fixed immediately and recorded.
For major issues that can't be repaired in-house contact as relevant the electrician Waitaki Electrical on 0800 277 244, or Ahoy Engineering on 0210 300 944. Waterforce Oamaru can supply parts for self repair.
If a leak is detected in the effluent storage pond it must be emptied as soon as possible within the limits of the soil water deficit and the leak found and repaired.
A register of effluent complaints must be available to the Otago Regional Council on request. If a complaint is received use this form to collect the following information:
(a) The date, time, location, and nature of the complaint
(b) The name, phone number and address of the complainant – unless the complainant elects not to supply, this information
(c )Action taken by the consent holder to remedy the situation and any policies or methods put in place to avoid or mitigate the problem occurring again.