Section 6.6.4

Windows - Fixing

Windows shall be correctly located within the opening, with equally spaced margins against the structure and securely fixed.

  • Window frame straps fixed to block work using plug and screw.

  • Straps should be installed with a fall to the external.

  • Fitted within 150mm of the top and bottom and at a maximum 600mm centres.

  • Windows should be fitted centrally to the opening and packed out equally to all sides.

  • Seal around window and cavity closer to help prevent air leakage.

  • Window board securely fitted level with equally sized overhangs either side of the opening.

  • Window board must be protected.

  • Ensure that the area below the window board is sealed to prevent air leakage.

  • Insulated VDPC (vertical damp proof course) installed to bay window.

  • Foil insulation provided at the head of the window to prevent thermal bridging.

  • Cavity closer mitre at the corner to provide continuation of the thermal break, the fire rating provided and to help prevent moisture ingress.

  • Windows should be fitted level and square.

  • Each window must be fixed the same distance off the internal block work.

  • Extra-long fixing straps should be used to extend onto the internal blockwork to avoid puncturing the VDPC.

  • Seal around window and cavity closer to help achieve a successful air test.

  • Window board securely fitted level with equal overhang of the block work throughout the bay window.

  • Window board protection to be provided.

  • Ensure that underneath the window board is sealed to prevent air leakage.