Section 6.3.8

Sound Insulation

Separating walls and floors and rooms which contain a WC, shall be constructed and insulated with materials of suitable thickness and density to provide adequate resistance to the transmission of sound.

  • Party wall cavity construction to consist of 2 block courses with 100mm cavity.

  • Cavity must extend a minimum of 450mm below DPC.

  • Fully bedded joints with a flush pointed finish to both sides of the blockwork.

  • Ties must be set at 900mm horizontally and 450mm vertically.

  • Tie type A must be used on separating walls.

  • Medium dense blocks should be used in the party wall construction.

  • Use tie at 225mm vertical centres to tie in with thermal block used on the external walls.

  • Use ARC party wall cavity closer at the party wall junction.

  • Party wall cavity should be free of mortar droppings.

  • Party wall must extend 450mm above the ceiling line in the loft space.

  • Cavity must be closed off at the top of the party wall.

  • Joists built in solid at the party wall.

  • Joists must not project into the cavity.

  • Blocks to be fitted to the end of the joists.

  • Insulation is required between rooms that include a WC and habitable rooms.

  • Except in the bedroom where the WC is in the ensuite attached to the habitable room.

  • 25mm of mineral wool between the studs and 1 layer of 12.5mm plasterboard is required.

  • Alternatively, 2 layers of 12.5mm plasterboard and no insulation.

  • Isorubber sound protection layer placed on top of the concrete floor planks.

  • Isorubber flanking strip placed around perimeter and internal walls.

  • Minimum 50mm overlap required to isorubber with laps tapped.

  • Isorubber flanking strip must be trapped between the concreted floor and the skirting board.

  • Flanking strip must be turned down under the skirting on external walls.