Section 6.1.7

Insulation

Insulation is required in cavities to ensure the property meets the Building Regulations and TER of the property.
Retrospective insulation is the Knauf ‘Supafill 34’

  • For retrospective (retro fill) insulation where gas membranes are not installed, cavities must remain clear to allow the insulation to cascade down below DPC.

  • Where a gas membrane is installed, the cavities must be insulated below the gas membrane.

  • Before retro fill works can take place on site, the machinery needs to be calibrated and tested.

  • To place retro fill insulation into the cavities, holes must be drilled into the external walls from inside the property.

  • Designed drill patterns must be followed.

  • Insulation to be placed as per the design.

  • Once insulation has been completed, the drilled holes must be pointed up using mortar.

  • In areas of very severe wind exposure (shaded pink), partial cavity insulation should be provided within the cavity.

  • Note - Full fill insulation would not conform to NHBC Requirements in areas of very severe exposure.

  • Partial fill insulation should be fitted tightly against the internal leaf using retaining devices.

  • Wall ties should be set 450mm vertically and 600mm horizontally.

  • Insulation should be tightly abutting each insulation board and cavity closures.

  • Insulation should be neatly cut at corners and bends to ensure that the thermal performance is continuous.

  • Insulation should be neatly cut around lintels to ensure the risks of cold bridging are eliminated.

  • Where you have a tie, a small cut with a saw should be applied to ensure no gapping appears in the insulation.