Protected transformers (CSP Type)are available with a variety of protection options including a secondary
breaker with weak link for secondary fault and overload protection, a
primary weak link fuse, current-limiting fusing for high interrupting
ratings and limiting fault currents, and internal or external lightning
arresters.
Standard Ratings / Single Phase - 5, 10, 15, 25, 37.5, 50, 75, 100, 167, 250, 333 KVA
Standard High-voltage & insulation level (BIL)- 7620/13200Y BIL: 95KV
- 13200/22860Y BIL: 125KV
- 13800/23900Y BIL: 125KV
- 14400/24940Y BIL: 125KV
- 34500GrdY/19920 BIL: 150KV
Standard de-energized before operating the tap changer - Two - 2½% taps above and below rated voltage
Standard secondary voltage & insulation level (BIL) The basic insulation level (BIL) of the secondary voltage shall be 30 kV.- 120/240 (3 bushings)
- 240/480 (3 bushings)
- 120 (2 bushings)
- 277 (2 bushings)
Standard Accessories: - Externally operated off- load tap changer
- Pressure relief device
- Stainless Diagrammatic name plate
- Ground strap and bolt on Tank & LV
Standard Accessories for CSP Type : - Externally operated off- load tap changer
- Pressure relief device
- Stainless Diagrammatic name plate
- Ground strap and bolt on Tank & LV
- Surge Arrester
- Primary Protective Link
- Secondary breaker / with overload reset and signal light
|