Fisher positioner problem Due to limits set on the controller of this valve, it is prone to repeated cycling. This ultimately manifested itself in a worn or grooved cam-roller. This caused the beam to become dislocated from it's pivot point and serious beam-misalignment ensued here. I corrected this by replacing the grooved cam roller with a new one. Direct acting 3-15 P.S.I.G. air to open valve with cam "A" installed. This is a Fisher EZ globe valve, 2"X300# flanged. Used in low pressure natural gas service to supply our hot oil furnace. (We keep our oil at 400 deg. F) Valve, Lift Check
The flow comes from the left. It lifts the globe valve type (the manufacturer probably used some globe valve drawings/specs) "disc" and then goes out to the right. See also: pool pump check valve gate valve steam high vacuum valves valve butterfly valve fill pro toilet fill valve one way valves plastic relief valve test bench air valve manufacturers |