InterPSS Cloud Edition is currently hosted at the Google Cloud using the Google App Engine. After uploading a file in one of the supported formats, you can do the following analysis: If you want to save you case for future usage and access more advance InterPSS features, you need to login. Please contact support@interpss.org for a user account. Loadflow AnlysisThere are currently 4 loadflow methods [NR, NR+, PQ, PQ+] available. NR stands for the Newton method, PQ for the Fast Decouple method. The + indicating addtion features, including the following:
Contingency AnalysisInterPSS currently supports three types of contingency analysis: N-1 Analysis; N-1-1 Analysis and N-2 Analysis.
Open each branch in the power network and run complete AC loadflow analysis for each contingency.
First open each branch in the power network and run complete AC loadflow analysis for each contingency. Then for each N-1 contingency, open each branch with branch Mva rating violation and run complete AC loadflow analysis for each N-1-1 contingency.
Open all combination of two branches in the power network and run complete AC loadflow analysis for each N-2 contingency. The following three reports are generated after the analysis:
Non-converged loadflow case [ tolerance: 0.0010 pu ]
Bus Voltage Limit: [1.10, 0.85] The voltage margin report lists the lowest voltage for the bus for all contingencies and compare it with a Bus Low Voltage Limit. The description tells which contingency caused the lowest voltage. For example, [x]Bus110->Bus280(1) indicates that the open branchBus110->Bus280(1) contingency caused the lowest voltage.
Branch Id MvaFlow MvaRating P + jQ Margin DescriptionThe branch Mva margin report lists the most severe branch Mva rating violation, indicating with a - sign. The description tells which contingency caused the most severe branch rating violation. ODM TransformationDownload ODM Xml file.Sample Case
|